Functional description
© 2006 ABB STOTZ-KONTAKT GmbH
38
ABB i-bus
®
EIB / KNX
Start Scenes
Option: 1
…
8
…
15
The start scene of the dynamic operation is defined with this parameter.
Parameterisation of the selected scene is implemented in the “Scene”
parameter window.
Start scene hold time
Option: 1
s
…
5min
…
24h
The run time of the start scene is defined with this parameter. The run time
commences after the scene transition time which is parameterised in the
“Scenes” parameter window. After the operating time ends, the end scene
commences with its own operating time. See Figure 12 for the timing.
End Scene
Option: 1
…
9
…
15
The end scene of the dynamic operation is defined with this parameter.
Parameterisation of the selected scene is implemented in the “Scene”
parameter window. See Figure 13 for the timing.
End scene hold time
Option: 1
s
…
5min
…
24h
indefinitely
The run time of the end scene is defined with this parameter. The run time
commences after the scene transition time which is parameterised in the
“Scenes” parameter window. The dynamic device switches off after the run
time has elapsed. See Figure 13 for the timing. If the setting “indefinitely” is
selected, the lighting always remains at, for example, the minimum
brightness value (safety value). The sequence (staircase lighting) will run
again if the dynamic process is retriggered.
A very convenient warning time can be programmed at the end of the
staircase lighting time with the end scene transition time (second scene) and
the run time of the end scene.