81
9 years preventive maintenance
Following additional actions have to take place:
−
Replace the power interface board SDCS-
PIN-H of units T1 … T5 (DCT880-W0x-
0020-0x … DCT880-W02-0960-0x).
The SDCS-PIN-H is located between the
heat sink and the electronic tray. It
operates continuously, because it supplies
the unit’s electronics even when the load
current is switched-off. Therefore, all its
components are exposed to hot
conditions.
Additionally the electrolytic capacitors on
the SDCS-PIN-H are aging. The SDCS-
PIN-H also is equipped with several
capacitors, which are sensitive to high
ambient temperature.
−
Aging of the electronic card result in:
1. Damage other devices.
2. Trip the thyristor power controller and cause unexpected shutdown.
−
Replace the flat cables of all units T1 … T5.
Environmental conditions, especially temperature and humidity could cause corrosion on the contact
surfaces and embitterment of the insulation.
−
Aging of the flat cables result in:
1. Contact problems.
2. Flat cable insulation breaks.
Preventive Maintenance
3ADW000449R0101 DCT880 Service Manual e a
Summary of Contents for DCT880
Page 1: ...DCT880 Service Manual DCT880 Thyristor power controller 20 A 4160 A ...
Page 2: ......
Page 85: ...85 T2 160 A 245 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 86: ...86 T3 325 A 420 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 87: ...87 T4 550 A 740 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 88: ...88 T5 890 A 960 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Page 89: ......