DCS800-EP Installation and Start-Up Manual
Circuit breaker Protection (optional)
Instantaneous trip:
All Drives: Factory set at 300 pct of rated current
Thermal overload trip:
60 HP (DCS800-EP1-0125-05 and DCS800-EP2-0140-05) only: Factory set to 100
pct of rated current
Control transformer
10 – 150 HP: 250 VA, 230/460 Vac primary; 120 Vac secondary;
Available for customer use: zero Amps
AC or DC Contactor
10 – 300 HP: AC line contactor with (1) aux. N.O. contact for customer use: 6 Amps
@ 24 – 127 Vac or 24 Vdc
400 – 600 HP: DC armature (DB) contactor, 3 pole (2 N.O. , 1 N.C. main contacts)
with (1) aux. contact for customer use: 10 Amps @ 600 Vac or 0.2 Amps @ 600 Vdc