Cabinet cooling and air flow
Cabinets must be sized to accommodate minimum
clearances as described in the previous section and in the
DCS800 Hardware Manual.
The maximum interior cabinet ambient temperature must
not exceed 40°C.
See table below for heat dissipation requirements. Cooling air
enters the bottom of the drive module and exits at the top (see
diagram at right).
Panel heat dissipation
HP
Non-Regenerative (2Q)
Regenerative (4Q)
Total panel
watts loss
Total panel
watts loss
Type Code
without
inductor
with
inductor
Type Code
without
inductor
with
inductor
10
DCS800-EP1-0020-05
162
182
DCS800-EP2-0025-05
170
190
20
DCS800-EP1-0045-05
228
283
DCS800-EP2-0050-05
246
301
30
DCS800-EP1-0065-05
291
350
DCS800-EP2-0075-05
319
378
40
DCS800-EP1-0090-05
356
426
DCS800-EP2-0100-05
387
457
60
DCS800-EP1-0125-05
483
578
DCS800-EP2-0140-05
530
625
75
DCS800-EP1-0180-05
656
751
100
DCS800-EP2-0200-05
776
903
125
DCS800-EP1-0230-05
882
1017
DCS800-EP2-0260-05
960
1095
150
DCS800-EP1-0315-05
1074
1209
DCS800-EP2-0350-05
1168
1303
200
DCS800-EP1-0405-05
1326
–
DCS800-EP2-0450-05
1426
–
250
DCS800-EP1-0470-05
1551
–
DCS800-EP2-0520-05
1695
–
300
DCS800-EP1-0610-05
1996
–
DCS800-EP2-0680-05
2167
–
400
DCS800-EP1-0740-05
2334
–
DCS800-EP2-0820-05
2552
–
500
DCS800-EP1-0900-05
2982
–
DCS800-EP2-1000-05
3252
–
600
DCS800-EP2-1010-05
3305
–