ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
73
Table 8
List of errors
Error code
Description
Recommended actions
Ix LL
Input x low light
Degenerated LED at connected CSU-2/TVOC-2 unit. The unit in the
other end should be replaced.
Ix NL
Input x no light
Make sure that light is transmitted by units connected to the
optical input connector and that the optical cable is not damaged.
CS Lx/N
Current sensor Lx/N
Connect cable from current sensor.
IE PS
Internal error power supply
Check if auxiliary voltage to CSU-2 is low (>24VAC/DC), if not, it
is an internal power supply error in which case CSU-2 should be
replaced.
IE Ix
Internal error input x
CSU-2 should be replaced.
IE OO
Internal error optical output
IE DC
Internal error daisy chain
8.3.1
LED-lights
Table 9
LED on CSU-2
LED
Description
Recommended actions
Green
Power
Red
Over current
Red
Error
Yellow
Communication
Table 10 LED on current sensor inputs
LED
Description
Recommended actions
OFF
Current sensor inputs are not configured
Flashing Green
Current sensor cable are connected and configured
Red
Current sensor inputs are configured but not connected
Connect cables from current sensor
08
Summary of Contents for CSU-2LV
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ......
Page 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Page 18: ......
Page 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Page 30: ......
Page 38: ......
Page 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Page 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Page 70: ......
Page 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Page 76: ......
Page 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...