64
ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
6.7
Troubleshooting
6.7.1
Visual diagnostics
The yellow Com LED flashes when a Modbus request is
received.
6.7.2
Practice via modpoll [3]
Using the application modpoll [3] from a windows
environment, it is easy to communicate with CSU-2. To
read the status of CSU-2 unit, do the following:
1.
Download modpoll from [3]
2.
Connect CSU-2 to a PC with a USB-RS485 adapter
3.
Configure Modbus RTU according to the existing
network. In the example, we choose Modbus ID =
5, Baud rate = 19200 and Frame format is 8 bits,
even, stop 1.
4.
Execute modpoll from command prompt:
modpoll -m rtu -0 -a 5 -r 0x64 -c 1 -t 4 -b 19200 -d 8
-s 1 -p even -l 100 COM9
INFORMATION
According to
, system status can be read with
address 0x64. A USB-RS485 adapter is used for
Modbus RTU communication, and it is connected
to USB serial port COM9.
Figure 35
Example for Modbus RTU connection with modpoll as master
1SFC170020M0201
06
Summary of Contents for CSU-2LV
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ......
Page 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Page 18: ......
Page 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Page 30: ......
Page 38: ......
Page 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Page 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Page 70: ......
Page 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Page 76: ......
Page 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...