50
ABB
ARC GUARD SYSTEM™ – CSU-2LV/2MV INSTALLATION AND MAINTENANCE GUIDE
6.6.3.3
Active errors
Currently active errors, bit is set if error is active.
ACTIVE_ERRORS
0x65
Bit
15–10
9
8
7
6
5
4
3
2
1
0
-
Internal
error
power
supply
Internal
error
optical
output
Internal
error
daisy
chain
Internal
error
input 1
Input 1
low light
Input 1 no
light
Rogowski
coil N
Rogowski
coil L3
Rogowski
coil L2
Rogowski
coil L1
Activation times for active errors register. If an error is
inactive, the time is for the last time the error occurred. If
error never has occurred the register is set to 0xFFFF.
Parameter name
Register access
Remark
ERROR_ACTIVATE_YEAR_MONTH_1
0x92 (R)
Rogowski coil L1
ERROR_ACTIVATE_YEAR_MONTH_2
0x95 (R)
Rogowski coil L2
ERROR_ACTIVATE_YEAR_MONTH_3
0x98 (R)
Rogowski coil L3
ERROR_ACTIVATE_YEAR_MONTH_4
0x9B (R)
Rogowski coil N
ERROR_ACTIVATE_YEAR_MONTH_5
0x9E (R)
Input 1 no light
ERROR_ACTIVATE_YEAR_MONTH_6
0xA1 (R)
Input 1 low light
ERROR_ACTIVATE_YEAR_MONTH_7
0xA4 (R)
Internal error input 1
ERROR_ACTIVATE_YEAR_MONTH_8
0xA7 (R)
Internal error daisy chain
ERROR_ACTIVATE_YEAR_MONTH_9
0xAA (R)
Internal error optical output
ERROR_ACTIVATE_YEAR_MONTH_10
0xAD (R)
Internal error power supply
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Years since 2000
Month (1 - 12)
Parameter name
Register access
Remark
ERROR_ACTIVATE_DATE_HOUR_1
0x93 (R)
Rogowski coil L1
ERROR_ACTIVATE_DATE_HOUR_2
0x96 (R)
Rogowski coil L2
ERROR_ACTIVATE_DATE_HOUR_3
0x99 (R)
Rogowski coil L3
ERROR_ACTIVATE_DATE_HOUR_4
0x9C (R)
Rogowski coil N
ERROR_ACTIVATE_DATE_HOUR_5
0x9F (R)
Input 1 no light
ERROR_ACTIVATE_DATE_HOUR_6
0xA2 (R)
Input 1 low light
ERROR_ACTIVATE_DATE_HOUR_7
0xA5 (R)
Internal error input 1
ERROR_ACTIVATE_DATE_HOUR_8
0xA8 (R)
Internal error daisy chain
ERROR_ACTIVATE_DATE_HOUR_9
0xAB (R)
Internal error optical output
ERROR_ACTIVATE_DATE_HOUR_10
0xAE (R)
Internal error power supply
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Date (1 - 31)
Hour (0 - 23)
06
Summary of Contents for CSU-2LV
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 12: ......
Page 17: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 17 03 ...
Page 18: ......
Page 29: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 29 04 ...
Page 30: ......
Page 38: ......
Page 66: ...66 ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 06 ...
Page 69: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 69 07 ...
Page 70: ......
Page 75: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 75 08 ...
Page 76: ......
Page 83: ...ABB ARC GUARD SYSTEM CSU 2LV 2MV INSTALLATION AND MAINTENANCE GUIDE 83 09 ...