16
CP620, CP630, CP635, CP651, CP661, CP665, CP676
Installation Environment
The equipment is not intended for continuous exposure to direct sunlight. This might accelerate the aging
process of the front panel film.
The equipment is not intended for installation in contact with corrosive chemical compounds. Check the
resistance of the front panel film to a specific compound before installation.
Do not use tools of any kind (screwdrivers etc.) to operate the touchscreen of the panel.
In order to meet the front panel protection classifications, proper installation procedure must be followed:
The borders of the cutout must be flat.
The cutout for the panel must be of the dimensions indicated in this manual.
Screw up each fixing screw until the plastic bezel corner get in contact with the panel.
The IP66 is guaranteed only if:
Maximum deviation from the plane surface to the cut-out:
0.5 mm
Thickness of the plate the equipment is mounted: 1.5 mm to 6 mm
Maximum surface roughness where the gasket is applied:
120 µm
Applying the Gasket
Apply the gasket on the rear of the frame.
NOTE
If the mounting surface is not plane and robust enough, the degree IP69K is not guaranteed.
A special mounting flange is included to provide the necessary support.
CP620, CP630, CP635
CP650, CP661, CP665, CP676
including –x(-WEB) versions
including –x(-WEB) versions
A
Gasket
B
Installation cut-out