CoreSense Hub option
B65
Risks of overloading a transformer
There are risks associated with overloading a transformer beyond its nameplate values. These are covered in
the IEC 60076-7 standard and summarized the table below.
—
Table 11
Factors increasing the risks of premature failure
Increased temperature
the temperature of the windings, cleats, leads, insulation and oil will increase and can reach
unacceptable levels.
Increased leakage flux
the leakage flux density outside the core increases, causing additional eddy current heating in
metallic parts linked by the leakage flux.
Increased gas and moisture
as the temperature changes, the moisture and gas content in the insulation and in oil will
change.
Risks on accessories
Bushings, tap-changers, cable-end connections and current transformers will also be exposed
to higher stresses which encroach upon design and application margins.
SCADA communication
For SCADA communication, CoreSense Hub uses the Modbus TCP protocol. This is similar to the standard
CoreSense but with specific register blocks for each external sensor linked to the CoreSense Hub. See
“Appendix C” on page C77 for more information on the standard Modbus parameters. Table 12 presents the
updated Modbus TCP interfaces between the CoreSense Hub to the SCADA.
—
Table 12
Modbus TCP interfaces from CoreSense Hub to SCADA
Register
Modbus
address
Parameter
Function
Data type
Access
Status/Alarms
0
Not supported
0–10
Reserved for future use
Information
11–20
40011
Model number
aSCII string
R
21–30
40021
Serial number
aSCII string
R
31–40
40031
Software version
aSCII string
R
41–50
40041
System ID
aSCII string
R
51
40051
Manufacturing date
high byte = month
low byte = day
32-bit binary value
R
52
40052
Year
R
Measurement
53
40053
hydrogen (ppm)
signed 16 bit binary number
R
54
40054
hydrogen RoC
(ppm/day)
may need scaling
signed 16 bit binary number
R
55
40055
RESERVED–hydrogen RoC
(ppm/week)
return 0
signed 16 bit binary number
R
56
40056
RESERVED–hydrogen RoC
(ppm/month)
return 0
signed 16 bit binary number
R
57
40057
Oil temperature (moisture)
(Celsius)
signed 16 bit binary number
R
58
40058
Moisture (aw)
scaled by 100
signed 16 bit binary number
R
Summary of Contents for CoreSense
Page 1: ... USER GUIDE CoreSense Hydrogen and Moisture Sensor ...
Page 10: ...Page intentionally left blank ...
Page 32: ...Page intentionally left blank ...
Page 43: ... Configuring the sensor head 39 About dialog box Figure 23 About dialog box ...
Page 48: ...Page intentionally left blank ...
Page 58: ...Page intentionally left blank ...
Page 80: ...Page intentionally left blank ...
Page 84: ...Page intentionally left blank ...
Page 106: ...Page intentionally left blank ...
Page 108: ...Page intentionally left blank ...
Page 110: ...Page intentionally left blank ...
Page 114: ...Page intentionally left blank ...
Page 120: ...Page intentionally left blank ...
Page 121: ......