ADDRESSABLE PARAMETERS
…7.2 COMMANDER 100/V100 – Registers
7.2.3 Set Points
Register
Variable Label
Read/Write
Limits/Values
40
Set Point High
RW
–999 to 9999
41
Set Point Low
RW
–999 to 9999
42
Local Set Point
RW
–999 to 9999
44
Remote Set Point Input
R
–999 to 9999
45
Fixed Set Point 1
RW
–999 to 9999
46
Fixed Set Point 2
RW
–999 to 9999
47
Fixed Set Point 3
RW
–999 to 9999
48
Fixed Set Point 4
RW
–999 to 9999
7.2.4 Alarm Settings
Register
Variable Label
Read/Write
Limits/Values
51
Alarm Trip 1
RW
–999 to 9999
53
Alarm Trip 2
RW
–999 to 9999
56
Alarm Hysteresis Value
RW
0 to 100
0 = None
1 = High Process
2 = Low Process
57
Alarm Type 1
R
3 = Not Valid
58
Alarm Type 2
R
4 = Not Valid
5 = High Deviation
6 = Low Deviation
7 = Loop Break
7.2.5 Ramp/Soak Settings
Register
Variable Label
Read/Write
Limits/Values
65
Ramp/Soak Run
W
1 = Run
66
Ramp/Soak Hold
W
1 = Hold
67
Ramp/Soak Skip
W
1 = Skip
68
Ramp/Soak Stop
W
1 = Stop
0 = Stop
69
Program Status
R
1 = Run
2 = Hold