ADDRESSABLE PARAMETERS…
…7.2 COMMANDER 100/V100 – Registers
7.2.2 Control Settings
Register
Variable Label
Read/Write
Limits/Values
12
Process Variable Input
R
–999 to 9999
13
Control Set Point
R
–999 to 9999
14
Output 1
RW*
–80 to 1100
15
Auto/Manual State
RW
0 = Auto; 1 = Manual
0 = Local
1 = Remote
2 = Fixed Set Point 1
16
Set Point Select
RW
3 = Fixed Set Point 2
4 = Fixed Set Point 3
5 = Fixed Set Point 4
6 = Ramp/Soak
17
Output 2
RW*
–80 to 1100
18
Fixed Set Point 1
RW
–999 to 9999
19
Fixed Set Point 2
RW
–999 to 9999
20
Fixed Set Point 3
RW
–999 to 9999
21
Fixed Set Point 4
RW
–999 to 9999
22**
Valve Deadband
RW
1 to 9999
23**
Valve Travel Time
RW
1 to 5000 sec
24**
Valve Drive
RW*
0 = Close
1 = Stop
2 = Open
25
Proportional Band 1
RW
1 to 9999
26
Integral Action Time
RW
0 to 7200
27
Derivative Action Time
RW
0 to 9999
28
Manual Reset
RW
0 to 1000
29
Cycle Time 1
RW
9 to 3000
30
Cycle Time 2
RW
9 to 3000
31
Proportional Band 2
RW
1 to 9999
32
Overlap
RW
100 to –100
33
Control Mode 1 (Heat)
R
0 = On/Off
34
Control Mode 2 (Cool)
R
1 = Analog Control***
2 = Time Proportioning
35
Control Output 1 Action
RW
0 = Reverse; 1 = Direct
36
Auto/Manual State
RW
0 = Auto; 1 = Manual
*
These registers can only be written to when the controller is in Manual Mode.
Control outputs 1 and 2 are only applicable to C100 instruments.
** V100 Instruments only
*** Control Mode 1 only