Taps or spurs in the feeder
If the protected feeder consists of taps or spurs, the measured fault impedance corresponds
to several physical fault locations (For example, A or B in Figure 4.3-34).
The actual fault location must be identified using additional information, for example,
short circuit current indicators placed on tapping points.
fault_on_distribution_line_with_spurts.png
Figure 4.3-34 Fault on a distribution line with spurs
Fault report function SCEFRFPR
This is a fault package report creating function block, It will create a report every time
a fault package is generated.
All monitored fault data will be recorded in the report including: Triggering, fault type,
un-supply time, breaks, phase, fault current, load current, Resistance, capacitance, fault
distance, validity, etc.
This report function will provide the report that COM600 WebHMI can handle and
present to the user.
Base Values
4.4.
In this function block, some of the settings are set in per unit (pu). These pu values are
relational to certain base values, for example the values given in A, kV and kVA. The
IED supports alternative base value groups for the phase current or voltagerelated settings,
36
1MRS758734
COM600 series 5.1
Substation Analytics Technical Manual