The fault distance calculation algorithm for the three-phase fault impedance loop is
defined by using the setting Load Com PP loops = "Disabled"/"Enabled" and setting
Simple mode PP loops = "Disabled"/"Enabled" setting.

The load compensation can be enabled or disabled with the Load Com PP loops =
FALSE/TRUE setting. The load compensation should be disabled only if the ratio between
the fault current and load current is large or when the value of the fault distance estimate
for the short circuit fault is required for each shot of an autoreclosing cycle.

The fault distance calculation is the most accurate when the calculation is made with the
fault loop model. This model requires positive sequence impedances as initial data. If
the data is not accessible, then the calculation can be made with a simple fault loop model
that does not need any impedance data. The simple fault loop model is enabled, with the
value Simple mode PP loops = TRUE. When the simple model is enabled, the conversion
of electrical fault distance into a physical distance is not done in the IED and the
FLT_DISTANCE output is not valid. The estimated impedances are still calculated and
shown normally in their respective outputs.

The function calculates XFPHASE, which is the positive sequence fault reactance in
primary ohms and is available as an output.

Table 4.3-1 Explanation of variations

Description

Abbreviation

Estimated fault loop resistance in primary ohms

RFLOOP

Estimated fault reactance in primary ohms

XFLOOP

Positive sequence fault reactance in primary
ohms

XFPHASE

Estimated fault resistance in primary ohms

RF

Positive sequence resistance from the substa-
tion to the fault location

R1

Positive sequence reactance from the substa-
tion to the fault location

X1

Earth return path resistance from the substation
to the fault location = (R0 - R1)/3

RN

Earth return path reactance from the substation
to the fault location = (X0 - X1)/3

XN

Zero sequence resistance from the substation
to the fault location

R0

Zero sequence reactance from the substation
to the fault location

X0

Physical fault resistance at the fault location. In
case of earth faults, it includes the arc and the
earthing resistance. In case of the phase-to-
phase faults, it equals to the arc resistance
between the phases. In case of three-phase
faults, it equals to the arc resistance per phase.

Rfault

22

1MRS758734

COM600 series 5.1

Substation Analytics Technical Manual

Summary of Contents for COM600 series

Page 1: ...COM600 series 5 1 Substation Analytics Technical Manual...

Page 2: ......

Page 3: ...ion 11 3 2 5 IEC 61850 Main Application 11 3 3 Circuit Breaker Condition Monitoring Application Design 11 3 3 1 Circuit breaker Condition Monitoring Application Design 11 3 3 2 SCBE Trigger Applicatio...

Page 4: ...ct travel time 46 5 4 2 Breaker contact travel time 47 5 5 Circuit breaker operation monitoring and operation counter 49 5 5 1 Circuit breaker operation monitoring and operation counter 49 5 5 2 Opera...

Page 5: ...be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This pro...

Page 6: ...ionality descriptions and lists function blocks logic diagrams input and output signals setting parameters and technical data sorted per function The manual can be used as a technical reference during...

Page 7: ...t point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The corresponding icons should be interpreted as follows T...

Page 8: ...18 Functions codes and symbols 1 9 ANSI IEEE Identification IEC 60617 Identi fication IEC 61850 Identi fication Function Description CBCM 1 CBCM 1 SSCBR1 Circuit breaker condition monitoring 21FL FLOC...

Page 9: ...analytics can be mapped onwards to slave protocols such as IEC 104 The COM600 analytics applications are designed to run on demand whenever there is data available from the IEDs which the application...

Page 10: ...data points coming from the IED One trigger condition is autorecloser status When a new reclosing sequence starts the analytics is launched to calculate unsupplied time In addition to unsupplied time...

Page 11: ...s Circuit Breaker Condition Monitoring Application Design 3 3 Circuit breaker Condition Monitoring Application Design 3 3 1 The circuit breaker condition monitoring consist of seven different main app...

Page 12: ...rcuit breaker inactivity and operations count calculations If comtrade data is available it will additionally produce circuit breaker accumulated energy data and circuit breaker trip time calculation...

Page 13: ...ll three currents and phase to earth voltages are measured The fault distance calculation is done in two steps The fault type is determined first using the build in Phase Selection Logic PSL After thi...

Page 14: ...respectively For cases where positive sequence components or phase to phase signals are used for fault distance indication the corresponding threshold values are scaled accordingly to the one third o...

Page 15: ...BC Fault or CA Fault is used for calculation When the faults are located at different feeders the phase to earth loop either AG Fault or BG Fault or CG Fault corres ponding to the faulty phase at the...

Page 16: ...t BG Fault or CG Fault are used for single phase to earthfaults When the individual earth faults are located at different feeders they are also applied in the case of a phase to phase to earth fault I...

Page 17: ...earthed systems where the fault current is fed from one side only and there are no in feeds along the protected line Load modelling takes into account the effect of the load in measured currents and...

Page 18: ...f the entire load is tapped at the end of the feeder where s proportional line length equals unity This value can be taken from anetwork calculation program The Equivalent load Dis parameter can be de...

Page 19: ...on simulation and field tests when Rfault 0 ohm the calculated equation_8 png Figure 4 3 11 Equation 8 The low ratio affects also the validity estimate of calculated fault distance which can be read...

Page 20: ...Com PP loops FALSE TRUE setting The load compensation should be disabled only if the ratio between the fault current and load current is large or when the value of the fault distance estimate for the...

Page 21: ...e 4 3 19 Fault loop impedance for a three phase fault impedance loop ABC Fault The three phase fault distance is calculated with a special measuring element using positive sequence quantities This is...

Page 22: ...e estimated impedances are still calculated and shown normally in their respective outputs The function calculates XFPHASE which is the positive sequence fault reactance in primary ohms and is availab...

Page 23: ...fault x xfault xpre fault The Pre fault time setting is used for generating the delta quantities The pre fault values are captured at least Pre fault time earlier than the actual fault moment occurs L...

Page 24: ...21 The behavior of fault distance estimate in time The actual trigger time is saved in the registers recorded data The trigger method is defined with the control parameter Calculation Trg mode with t...

Page 25: ...curs 200 ms 40 ms 160 ms after PSL has recognized the fault condition 40 ms is reserved for the PSL function for identifying the fault type PSL is a non directional function and therefore internal tri...

Page 26: ...reclosing function which indicates that the autoreclosing sequence is in progress with the BLOCK input of SCE FRFLO Blocking of the SCEFRFLO triggering is suggested during the autoreclosing sequence w...

Page 27: ...LIDITY output values Indicator is not applicable fault type is a short circuit N A Result is not affected by error sources High Result is slightly affect by error sources The additional error in the f...

Page 28: ...and the FLT_DISTANCE output is not valid If the impedance settings are in use it is important that the settings closely match the impedances through which the fault current flows The impedance setting...

Page 29: ...itive sequence impedance values An accurate fault localization requires good setting values for line impedances As datasheet impedance per unit values are valid only for a certain tower configuration...

Page 30: ...t are sufficient The positive sequence impedance per unit values for the lines are known or can easily be obtained from datasheets The zero sequence values are not so easy to obtain as they depend on...

Page 31: ...n accuracy for earth faults They are critical for an accurate fault location in unearthed networks In other types of networks they are less critical The Ph leakage Ris setting represents the leakage l...

Page 32: ...ce per phase can be calculated equation_20 png Figure 4 3 31 Equation 20 Ux phase to earth voltage SCEFRFLO can also determine the value for the Ph capacitive React setting by measure ments The calcul...

Page 33: ...be used for the SCEFR FLO block activation to disable wrong value calculation The delay TONGAPC must be set longer than the start delay of the directional earth fault function DEFLPDEF inside the term...

Page 34: ...A parameter corresponding to the total line length Other longitudinal impedance settings are disabled sections B and C If Num of line sections 1 the longitudinal impedance settings R1 line section A X...

Page 35: ...setting assumes homogeneous line while the model with three impedance settings gives accurate non homogeneous line with three sections These parameters are given in Table 4 3 1 Table 4 3 1 Impedance d...

Page 36: ...block It will create a report every time a fault package is generated All monitored fault data will be recorded in the report including Triggering fault type un supply time breaks phase fault current...

Page 37: ...upported time 1 UNSUPP_TIME Record data of bank 1 for Fault phase 1 FLT_PHASE Record data of bank 1 for Fault type 1 FLT_TYPE Record data of bank 1 for Validity of the calcu lation 1 VALIDITY_CALC Rec...

Page 38: ...FLO requires three phase currents for operation The phase currents can be measured with conventional current transformers or Rogowski coils The full operation of SCEFRFLO requires that all three phase...

Page 39: ...IL1 Phase B Current fault location calculation input 0 DOUBLE R_IL2 Phase C Current fault location calculation input 0 DOUBLE R_IL3 CB Position blocking logic False BOOLEAN R_CB_POS Table 4 8 2 SCEFRL...

Page 40: ...ays equal to the current value at Input 1 1 Type new para here 0 2147483647 DelayCycles Detect changes of Input to true True 1 Type new para here False True Detec tRaisingEdge Detect changes of Input...

Page 41: ...Phase voltage Meas Trigger mode for distance calculation Continuous 1 Type new para here External Internal Continuous Calculation Trg mode High alarm limit for calcu lated distance 1 000 0 001 Pu 0 00...

Page 42: ...section B Positive sequence line reactance line section B 1 0 001 Ohm pu 0 001 1000 X1 line section B Zero sequence line resistance line section B 4 0 001 Ohm pu 0 001 1000 R0 line section B Zero sequ...

Page 43: ...tType if FaultLoopValid is false 2 1 Type new para here Type new para here Substitute FaultType Interval between the executions ms 20 1 Ms Type new para here Interval Monitored Data 4 10 Table 4 10 1...

Page 44: ...ere 0 2147483647 INTEGER WR_PHASE Implementation method Type new para here 0 2147483647 INTEGER WR_IMP_METHOD Source LN Type new para here 0 2147483647 STRING WR_SRC_LN IED name Type new para here 0 2...

Page 45: ...gy is calculated from the measured input currents as a sum of Iy t values Alarms are generated when the calculated values exceed the threshold settings The function contains a blocking functionality I...

Page 46: ...el time 5 4 Circuit breaker status and breaker contact travel time 5 4 1 The Circuit breaker status sub function monitors the position of the circuit breaker that is whether the breaker is in open clo...

Page 47: ...travel time 5 4 2 The Breaker contact travel time module calculates the breaker contact travel time for the closing and opening operation The operation of the breaker contact travel time measurement...

Page 48: ...et the actual opening time This factor is added with the Opening time Cor t1 t2 setting The closing time is calculated by adding the value set with the Closing time Cor t3 t4 setting to the measured c...

Page 49: ...as remained inactive that is has stayed in the same open or closed state The calculation is done by monitoring the states of the POSOPEN and POSCLOSE auxiliary contacts The inactive days INA_DAYS is a...

Page 50: ...into use by writing the value to the Counter initial Val parameter and by setting the parameter CB wear values in the clear menu from WHMI or LHMI The set values will be taken into use when trigger a...

Page 51: ...ns If the setting is positive the calculation of energy starts after the auxiliary contact has opened and when the delay is equal to the value set with the Difference Cor time setting When the setting...

Page 52: ...ry inputs SPR_CHR_ST and SPR_CHR indicate spring charging started and spring charged respectively The spring charging time is calculated from the difference of these two signal timings The spring char...

Page 53: ...binary input BLOCK can be used to block the function The activation of the BLOCK input deactivates all outputs and resets internal timers The alarm signals from the function can be blocked by activati...

Page 54: ...n oil circuit breaker The change of state can be detected from the binary input of the auxiliary contact There is a possibility to set an initial value for the counter which can be used to initialize...

Page 55: ...set value 0 BOOLEAN TrvTOpAlm CB close travel time exceeded set value 0 BOOLEAN TrvClAlm Number of CB opera tions exceeds alarm limit 0 BOOLEAN CbOprAlm Remaining life of CB exceeded alarm limit 0 BOO...

Page 56: ...600 1 Hz SamplingFre quency Time delay to delay the pressure alarm s 0 1 1 S 0 60 Gas Pressure Alarm Time Time delay to delay the pressure lockout s 0 1 1 S 0 60 Gas Pressure Lockout Time Initial accu...

Page 57: ...oring Alarm Level Operations alarm level 200 1 Count 0 9999 CB Operation Number Alarm Level Operations lockout level 300 1 Count 0 999 CB Operation Lockout Level Reset operation number False 1 Reset F...

Page 58: ...to position change 1 Open command to position change Calculation from CB Binary Signals Travel Time Calcu lation Mode Technical revision history 5 12 Table 5 12 1 SSCBR Technical revision history Cha...

Page 59: ......

Page 60: ...Phone 358 10 22 11 ABB Distribution Automation 4300 Coral Ridge Drive Coral Springs Florida 33065 Phone 1 954 752 6700 www abb com mediumvoltage www abb com substationautomation 1MRS758734 B 9 4 2018...

Reviews: