20 CDPI-01 communication adapter module
Start-up
Before you start
Make sure that you have completed the drive start-up.
Setting the parameters – Example for ACS580
Standard control program
If the communication adapter module is used to chain a control
panel or a PC to several drives, set the parameters of group 49
Panel port communication for each drive before you connect the
drives to the bus.
1. Power up the drive.
2. Define the node ID of the drive (
49.01 Node ID number
).
All devices connected to the bus must have a unique node ID.
It is advisable to reserve ID 1 for spare/replacement drives
because they have ID 1 as the default factory setting. Start
numbering from ID 2.
3. Set the baud rate of the drive (
49.03 Baud rate
).
The baud rate has to be the same for all nodes on the bus.
4. Select a suitable value for parameter
49.05 Communication
loss action value
.
This parameter defines the operation of the drive when the
control panel communication breaks.
•
No action (0):
No action taken.
•
Fault (1):
Drive trips on a fault.
•
Last speed (2):
Drive freezes the speed to the level the
drive was operating at.
•
Speed ref safe (3):
Drive sets the speed to a safe speed
reference.