CDPI-01 communication adapter module 13
Alternative 2: Routing the cabling outside the drive
If you have several drives on the panel bus, repeat these steps in
all drives.
1. If the drive is running, stop the drive.
2. Make a hole for the panel cable on the left side of the
communication adapter module.
If you need to chain the panel bus to another drive, make a
hole for the chaining cable as well.
3. Connect the panel cable to module connector X101.
If you need to chain the panel bus to another drive, also
connect the chaining cable to module connector X102.
4. Adjust the switches at the back of the module.
Termination switch (S100):
•
If the module is connected to one drive only, set the switch
to OFF.
•
If you have several drives on the panel bus, set the switch
to ON in the last module of the bus, OFF in all other
modules. The control panel terminates the bus at its end,
so only the other end of the bus must be terminated.
Bias switch (S101): Must be OFF in all modules.
5. Attach the module to the drive.
•
Lead the cable(s) through the hole(s) to the front side of
the module (a).
•
Place the bottom end of the module into the bottom of the
slot in the drive (b).
•
Pivot the module and push the upper part (c) until you hear
a click.
6. Secure the cable(s) to applicable cable supports.
For a panel bus chaining example, see section
on page