Safety Relay

C6702

DIN EN / IEC 60947-5-1

Operating Instructions

Order No.: 2CDC 113 025 M9701

English

2

The safety relay must be installed in switchgear cubicles complying 
with degree of protection IP32, IP43 or IP54, depending on the prevailing 
environmental conditions.

The products described herein are designed to be components of a customized 
machinery safety-oriented control system. A complete safety-oriented system 
may include safety sensors, evaluators, actuators and signaling components. It 
is the responsibility of each company to conduct its own evalution of the effec-
tiveness of the safety system by trained individuals. ABB AG, its subsidiaries 
and affiliates (collectively "ABB") are not in a position to evaluate all of the cha-
racteristics of a given system or product or machine not designed by ABB. 
ABB accepts no liability for any recommendation that may be implied or stated 
herein. The warranty contained in the contract of sale by ABB is the sole war-
ranty of ABB. Any statements contained herein do not create new warranties or 
modify existing ones.

The C6702 safety relay can be used in EMERGENCY STOP devices according to 
DIN EN / IEC 60947-5-5 and in safety circuits according to 
DIN EN / IEC 60204-1, e.g. in movable guards and protective doors or in non-
contact protective devices in accordance with DIN EN / IEC 61496-1 , electrical 
equipment for furnaces in accordance with DIN EN 50156-1 and automatic firing 
systems for gas burners in accordance with DIN EN 298 . Depending on the 
external circuit, max. Performance Level PL e / Cat. 4 according to 
DIN EN ISO 13849-1 and/or SIL 3 according to IEC 62061 can be achieved. The 
user must carry out an evaluation of the overall systems.

 

The C6702 solid-state safety relay has one safe solid-state output and one time-
delayed safe solid-state output. Three LEDs indicate the operating state and the 
function. 
When the device is put into operation it runs through a self-test to test the 
correct functioning of the internal electronics. All internal circuit components 
are monitored for faults cyclically during operation. 
Connect the EMERGENCY STOP button and/or the position switches or light 
arrays to terminals Y11, Y12 and Y21, Y22. Connect the ON button in series with 
the NC contacts of the external actuators to the supply voltage L+ (24 V DC) and 
to terminal Y34. Connect cascading input 1 either via a safe output or directly to 
the supply voltage L+ (24 V DC). 
External actuators or loads can be switched via safe outputs 14, 24. It must be 
ensured that the actuators or loads and the C6702 electronic safety relay have 
the same frame potential. Paralleling outputs 14 and 24 to increase the load cur-
rent is not permissible. 
If electronic sensors (light-array monitoring, etc.) are used, and in single-channel 
operation, Y35 must be connected to L+ (24 V DC). For autostart operation, Y32 
must be connected directly to L+ (24 V DC) and Y34 must be connected to it via 
NC contacts of the external actuators.

Use a power pack to IEC 60536 safety class III (SELV or PELV) 
for power supply!

1

)

Sensor circuits open; Cross-circuit between the sensors; Short-circuit of sensors to frame

2

)

only when using circuit variant with "cross-circuit detection"

3

)

Safe outputs disconnected for test purposes; sufficiently slow actuators are not 

affected.

4

Delay time running

For further data and accessories see Catalog.

Read and understand these instructions before installing, 

operating, or maintaining the equipment. 

 DANGER

Hazardous voltage.

Will cause death or serious injury.

Turn off and lock out all power supplying this device before working 

on this device.

CAUTION

Reliable functioning of the equipment is only ensured with certified compo-

nents.

IMPORTANT NOTICE

Application

Functional description and instructions for connection

Terminal 
assignments

Operating 
voltage

A1 
A2

L+ 
M

Sensors

Y11, Y12
Y21, Y22
Y35
Y32
Y34

Channel 1 EMERGENCY STOP or position switch
Channel 2 EMERGENCY STOP or position switch
With / without cross-circuit detection
Autostart
ON button, feedback circuit 

Input
Outputs

1
14
28

Cascading input
Safe solid-state output
Safe solid-state output, time-delayed

!

Cable lengths

for 2 x 1.5 mm

2

max. 2000 m (total cable length for sensors)

Figures

Fig. I/Ia: Dimension drawings (dimensions in mm) / Terminal designation
Fig. II:

Installation / Connection

Fig. IIIa: Safety data
Fig. IIIb: Application data
Fig. IV: Internal circuit: 

¿

 power pack, 

À

 sensors, 

Á

 Output 1, 

Â

 Output 2

Fig. V:

Protective-door monitoring, two-channel, autostart; 
with voltage-operated e.l.c.b. and delayed disconnection, stop

Fig. VI: EMERGENCY STOP, single-channel, monitored start with additional 

ON button; with voltage-operated e.l.c.b. and delayed disconnection, 
stop

Fig. VII: EMERGENCY STOP, two-channel, monitored start with additional ON 

button; with voltage-operated e.l.c.b. and delayed disconnection

Fig. VIII: EMERGENCY STOP, two-channel, monitored start with additional 

ON button and protective-door monitoring, two-channel, autostart

Fig. IX: Light-array monitoring, two-channel, autostart
Fig. X:

Safety mat, two-channel, autostart

Operating states

LEDs

Operation

POWER

RUN

FAULT

PS

EMERGENCY 
STOP

ON button

Outputs

ON

not activated was activated

on

activated

1

)

not activated

off

not activated not activated

off

flashes

4

)

activated not 

activated

off/on

on startup self-test approx. 7 sec.

Faults

flashes

• Defect in electronics
• Change in terminal assignment 

during operation

• Short-circuit to 24V

2)

off

No supply voltage

Technical data

Permissible ambient temperature T

Operation / storage

–25 to +60 °C / –40 to +80 °C

Degree of protection to DIN EN  / IEC 60529 IP40, IP20 at terminals
Rated insulation voltage

50 V

Rated impulse withstand voltage 

500 V

Rated control supply voltage

24 V DC

Rated power

1.3 W

Operating range

0.9 to 1.15 x U

s

Shock resistance (half-sine) as per 
DIN EN / IEC 60068

8

/ 10 ms

Weight

150 g

Recovery time after EMERGENCY STOP

min. 200 ms

Recovery time after power failure

7 s

Release time after EMERGENCY STOP

30ms/0.05 to 3s or 0.5 to 30s or 5 to 300s

Pickup time

max. 40 ms

Short-circuit protection

no fusing necessary!

Dark time

3)

<

1 ms

Start signal Y34

pulse (min.200 ms / max. 5 s)

PFH / SFF (%)

5,358x10

–11

 / 99,35 %

MTTR / T1

8 h / 10 Years

Utilization category 

as per IEC 60947-5-1

Rated operational 
voltage

 

Rated operational current

per output 

DC-13

24 V

1.5 A

Note! This product is obsolete. For replacement see Sentry safety relays.

Summary of Contents for C6702

Page 1: ... Verwenden Sie als Stromversorgung ein Netzteil nach IEC 60536 Schutzklasse III SELV oder PELV 1 Sensorkreise geöffnet Querschluss zwischen den Sensoren Kurzschluss der Sensoren nach Masse 2 nur bei Beschaltungsvariante mit Querschluss Erkennung 3 Testbedingtes Abschalten der sicheren Ausgänge hinreichend träge Aktoren bleiben unbeeinflusst 4 Verzögerungszeit läuft Weitere Daten und Bestellnummern...

Page 2: ...circuit between the sensors Short circuit of sensors to frame 2 only when using circuit variant with cross circuit detection 3 Safe outputs disconnected for test purposes sufficiently slow actuators are not affected 4 Delay time running For further data and accessories see Catalog Read and understand these instructions before installing operating or maintaining the equipment DANGER Hazardous volta...

Page 3: ...uits de capteurs ouverts Court circuit entre capteurs Court circuit entre capteurs et masse 2 uniquement pour variante de montage avec détection de court circuit 3 Coupure des départs protégés pour raison d essai les actuateurs suffisamment lents n en sont pas affectés 4 Temporisation en cours Pour de plus amples informations et pour les accessoires voir Catalogue Ne pas installer utiliser ou inte...

Page 4: ... IEC 60536 clase de protección III SELV ó PELV 1 Circuitos de sensor abiertos Corto entre sensores Cortocircuito de sensores a masa 2 sólo en la variante de conexión con detección de cortos entre polos 3 Desconexión de salidas seguras condicionada por pruebase no afecta a actuadores con inercia suficiente 4 Transcurriendo tiempo de retardo Para más datos y el Nº de referencia para accesorios v Cat...

Page 5: ...to tra sensori Cortocircuito dei sensori per massa 2 solo per la variante di cablaggio con riconoscimento cortocircuito 3 Disinserzione delle uscite sicure a fini di test gli attuatori sufficientemente lentinon vengono influenzati 4 Transcurriendo tiempo de retardo Per altri dati e per le sigle di ordinazione degli accessori vedere il catalogo Leggere con attenzione queste istruzioni prima di inst...

Page 6: ...curto circuito dos sensores segundo a massa 2 só em caso de ligação com identificação de contato transversal 3 desligamento das saídas seguras condicionado a teste atuadores suficientementelentos não são influenciados 4 tempo de temporização correndo Para mais informações e núm de encomenda consulte o catálogo Ler e compreender estas instruções antes da instalação operação ou manutenção do equipam...

Page 7: ... 82 6 92 2 101 6 II c a b d 1 U 0 V 2 a b c d 1SAR 390 000 R2000 6 6 7 3 4 5 1SAR 390 000 R1000 A C D B C6702 5 6 mm PZ2 0 8 1 2 Nm 7 to 10 3 lb in 1 x 0 5 4 0 mm 2 x 0 5 2 5 mm 2 x 0 5 1 5 mm 1 x 0 5 2 5 mm AWG 2 x 20 to 14 10 10 10 A C D B A B C D Kodiert Coded Codé Cifrado Codificato Codificado Note This product is obsolete For replacement see Sentry safety relays ...

Page 8: ... 1 3 PL DIN EN ISO 13849 c e Kat DIN EN ISO 13849 1 4 DE 1 max erreichbare Werte 2 1 kanalig 3 2 kanalig EN 1 max achievable values 2 single channel 3 two channel FR 1 valeurs max pouvant être atteintes 2 monocanal 3 bicanal ES 1 valores máximos que se pueden alcanzar 2 1 canal 3 2 canales IT 1 valori max raggiungibili 2 un canale 3 due canali PT 1 valores máximos atingíveis 2 um canal 3 dois cana...

Page 9: ...U M K1 K2 K1 K2 M L Y35 Y21 Y22 A2 14 28 A1 Y11 Y12 Y32 1 Y34 C6702 V K1 FU M K1 K1 M L Y35 Y21 Y22 A2 14 28 A1 Y11 Y12 Y32 1 Y34 C6702 ON VI K1 K2 FU M K1 K2 K1 K2 M L Y35 Y21 Y22 A2 14 28 A1 Y11 Y12 Y32 1 Y34 C6702 ON VII Note This product is obsolete For replacement see Sentry safety relays ...

Page 10: ...14 28 A1 Y11 Y12 Y32 1 Y34 C6702 Y35 Y21 Y22 A2 14 24 A1 Y11 Y12 Y32 1 Y34 C6701 L K1 K2 K1 ON VIII K1 K2 K1 K2 M L Y35 Y21 Y22 A2 14 28 A1 Y11 Y12 Y32 1 Y34 C6702 K2 FU M K1 Type 4 IEC CEI 61 496 1 IX K1 K2 M Y35 Y21 Y22 A2 14 28 A1 Y11 Y12 Y32 1 Y34 C6702 L K1 K2 K2 FU M K1 X ABB STOTZ KONTAKT GmbH Postfach 10 16 80 D 69006 Heidelberg Note This product is obsolete For replacement see Sentry safe...