SEt
SP–AdJ
YES
LSP–HI
1000
LSP–LO
0
LSPt
500
SPt–SL
YES
POINtS
SP–trK
no
Page Header –
Set Points
.
Set Point Adjustment Enable
This frame allows display and adjustment of the set point in
the
Operating Page Displays
(see
Section 5.2 of the
Operating Guide
)
. Select
YES
to enable or
no
to disable.
Set Point High Limit
This is the maximum value to which the local set point can
be adjusted.
Set the value required. The decimal point position is set
automatically.
Set Point Low Limit
This is the minimum value to which the local set point can
be adjusted.
Set the value required. The decimal point position is set
automatically.
Local Set Point Value
Set the value required, within the limits set above. The
decimal point position is set automatically to that set in the
Set Up Display Page
– see Section 4.8.
Set Point Tracking Enable
If
Set Point Tracking
is enabled and the controller is in
Manual mode the local set point tracks the process
variable. When the controller is in
Set Point Tracking
mode
the local set point limits can be exceeded. If the local set
point is outside of its limits when the tracking mode is
disabled, the local set point value can only be adjusted
towards its limits. Once within the limits they apply as
normal.
Select
YES
to enable or no to disable.
Set Point Select
This frame enables selection of set point type from the
Operating Page
i.e.,
LOCAL
,
rEMOtE
, or
dUAL
as
applicable – see
Set Point Type Selection
(
Section 5.2 of the
Operating Guide
)
.
Select YES to enable, or no to disable.