44
PU.
SCALE
tYPE
20.0
OUtPUt
rEt–HI
4.0
rEt–LO
AdJUSt
rEtrAN
4.12
Retransmission Output Page
Information.
•
Retransmission of process variable, set point, control output or position feedback input.
•
Programmable current output range.
•
Retransmission output can be used for cool output in heat/cool applications.
…4
CONFIGURATION
Page Header – Retransmisson Output.
Parameter Type
Select the parameter type to be re-transmitted,
PV
(process variable input),
SPt
(set point),
OUt
(output) or
PFb
(position feedback).
Retransmission Maximum
Set the maximum retransmission value, between 0.0mA
and 20.0mA in 0.1mA increments.
Retransmission Minimum
Set the minimum retransmission value, between 0.0mA
and 20.0mA in 0.1mA increments.
Return to top of
Retransmission Output Page
or
Advance to
Scale Adjustment Page.
Page Header – Cool Output Page
Cool Output Maximum
Set the maximum value for the cool output, between
0.0mA and 20.0mA in 0.1mA increments.
Cool Output Minimum
Set the minimum value for the cool output, between 0.0mA
and 20.0mA in 0.1mA increments.
Return to top of
Cool Output Page
or
advance to
Scale Adjustment Page
.
4.13
Cool Output Page
This page is only present if
HtCOOL
is selected at
Control Mode
and
C-ProP
is selected at
Second Output Type
in the
Set Up Control Page
– see Fig. 3.1 and Section 4.10.
OUtPUt
SCALE
20.0
COOL–HI
COOL
4.0
COOL–LO
AdJUSt
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com