21
4
CONFIGURATION…
…4.6
Set Up Remote Set Point Input Page
r–HI–2
rtd
tc–x
or
dEC–Pt
20.0
r–LO–2
4.0
FdLP–2
10.0
20.0
dEFACt
NONE
LOCAL
dF–SP
t
bSPd– 2
UP
dN
NONE
dEF–SPt
500.0
o r
SEtUP
dISPLY
PAGE
PSN–Fb
0
LIN–LO
NONE
LOCAL
or
dF-SPt
Linearizer Zero
Set the range minimum temperature in
°
C or
°
F as selected
at
Linearizer Units
above, within the limits detailed in Table
4.1.
Remote Set Point Range Full Scale
Set the remote set point range full scale value within the
limits in
Table 4.2
– see page 18.
Decimal Point
Set the decimal point position required for
both
the range
full scale and range zero values.
Input Range Zero
Set the remote set point range zero value required within
the limits in
Table 4.2
– see page 18.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
remote set point is driven according to the Broken Sensor
Protection Drive. Select the drive required:
NONE
for no
drive,
UP
for upscale drive or
dN
for downscale drive.
Fault Detection Level Percentage, Remote Set Point
This frame is as detailed in the
Fault Detection Level
Percentage, Process Variable Input
frame – see page 19.
Set the value required, between 0.0 and 100.0% in 0.1%
increments.
Default Action (Remote Set Point)
Select the default action required in the event of an error:
NONE
–
No default action.
LOCAL
–
The controller reverts to local mode
when an error is detected and the local
set point value is used.
dF–SPt
–
The controller reverts to local mode
when an error is detected and the set
point value changes to the
Default Set
Point
value below.
Default Set Point
Set the default set point value required in the event of an
error.
Return to top of
Remote Set Point Input Page
or advance to
the next programming page.