Operating Instructions
Busch-Wächter
®
Commissioning
Operating Instructions | 1473-1-8134
— 13 —
Pos: 34 /#Neustruktur#/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/1. Ebene/G - L/Inbetriebnahme @ 11\mod_1279185496977_15.docx @ 83035 @ 22222 @ 1
7 Commissioning
Pos: 35 /#Neustruktur#/Online-Dokumentation (+KNX)/Inbetriebnahme/Waechter/Inbetriebnahme - 6854 @ 25\mod_1340274623213_15.docx @ 219700 @ 222 @ 1
7.1
Setting the coverage
Use the following steps to set the coverage:
Fig. 10: Setting the coverage
1. Set the coverage of the device by turning the controller (1).
-
The sensor shifts when the controller is turned. The higher the setting of the sensor the smaller is the
coverage.
-
The adjustment range of the sensor ranges from 6 m (sensor position at the top) to a maximum of 12 m
(sensor position at the bottom).
7.2 Activation
test
Fig. 11: Control element
To carry out the activation test, perform the following steps:
1. Set selector switch to T/S.
-
The device is now in test mode for 10 minutes (daytime operation, switch-off delay 2 sec.). In addition,
each detection is indicated by the status LED flashing quickly.
-
After this, the device switches back to standard operating mode.
2. To carry out an additional activation test, set the selector switch back to position T/S or interrupt the operating
voltage supply for more than 15 seconds.
-
The device is now in test mode for another 10 minutes. Test mode is exited automatically after 10 minutes
or by adjusting the brightness.
The activation test has been carried out.
Pos: 36 /#Neustruktur#/Online-Dokumentation (+KNX)/Steuermodule - Online-Dokumentation (--> Für alle Dokumente <--)/++++++++++++ Seitenu+++++++++++ @ 9\mod_1268898668093_0.docx @ 52149 @ 333 @ 1
1
+
-
T/S
3
min
1
min
5
min