background image

4NWP100446R0001_OPM_ABB_AS400RelayCardPowerValue_EN140226

Page 5/15   ABB

Modifications reserved

1.3 

General Characteristics

The Relay Card is composed of 3 main contacts as show in Figure 2.

   (1)                                (2)

    (3)

Figure 2: Layout of the Relay Card

PCBA Size: 146.2 x 60 x 1.6 mm

(1) Dry contact connector

(2) RJ45 Connector for RS232

(3) UPS contact

Summary of Contents for AS400

Page 1: ...0001_OPM_ABB_AS400RelayCardPowerValue_EN140226 Page 1 15 ABB Modifications reserved AS400 Relay Card User Manual 4NWP100446R001_OPM_ABB_AS400RelayCardPowerValue_EN140226 doc Copyright 2014 ABB All rights reserved ...

Page 2: ...Positioning and Storage 4 1 2 1 Receipt of AS400 card and visual inspection 4 1 2 2 Unpacking 4 1 3 General Characteristics 5 1 3 1 Interface 14 pin Dry Contact Connector and RJ45 6 1 3 2 RJ45 to DB9 7 1 3 3 Interface with the UPS 7 1 4 Configuring the Card 8 1 4 1 Serial Data format 8 1 4 2 Installation 8 1 5 Setting operation menu 11 1 5 1 Password menu 11 1 5 2 Main menu 11 ...

Page 3: ...figure Dry contact active delay time This document specifies the Serial communication protocol of the AS400 Relay Card and guides the user throughout the available configurations Read carefully all instructions and save this manual for future reference 1 2 Delivery Transportation Positioning and Storage 1 2 1 Receipt of AS400 card and visual inspection Upon receiving the AS400 Relay Card carefully...

Page 4: ...e 5 15 ABB Modifications reserved 1 3 General Characteristics The Relay Card is composed of 3 main contacts as show in Figure 2 1 2 3 Figure 2 Layout of the Relay Card PCBA Size 146 2 x 60 x 1 6 mm 1 Dry contact connector 2 RJ45 Connector for RS232 3 UPS contact ...

Page 5: ...tput signal NO or NC Output signal NO or NC Output signal NO or NC Input signal The external contact must be closed between pin 8 and pin 1 Input signal The external contact must be closed between pin 14 and pin 1 Input signal The external contact must be closed between pin 7 and pin 1 RS232 RJ45 cable to DB9F TXD2 RXD2 GND RJ45 Pin 3 RJ45 Pin 6 RJ45 Pin 4 12Vdc 3mA Max 12Vdc 5mA Max GND Power sys...

Page 6: ...ERVE Table 2 Pin Assignment 1 3 3 1 Dry contact Functionality Output signals Segment 1 5 It is possible to choose one function for a Segment according to Table 3 Description 1 0 Utility Fail Fail Normal Battery Low Battery Low Normal General Alarm Alarm Normal Bypass Status Online UPS Or AVR Status Offline LIA UPS Bypass Active Or AVR Active Not Bypass Status Or Not AVR Status Summary Alarm Alarm ...

Page 7: ...escription 1 0 UPS Off OFF Normal Table 6 Input signal on Segment 8 1 4 Configuring the Card This chapter describes how to install connect and configure ABB s AS400 Card 1 4 1 Serial Data format AS400 Relay Card data has a 2400 baud rate and consist of 1 start bit 8 data bits no parity and 1 stop bit BAUD RATE 2400 band DATA LENGTH 8 bits STOP BIT 1 bit PARITY NONE Data format figure Start b0 b1 b...

Page 8: ... port on the computer Figure 6 Card Connection 1 4 2 2 Configuration To configure the card 1 Verify that the serial cable supplied is connected to the card s Settings port and the computer s COM port 2 Open your terminal emulation program such as HyperTerminal If you do not have it in your computer you can download it from our website http www newavenergy com files hypertrm zip a StartàAll Program...

Page 9: ...Modifications reserved 3 Name the new connection Figure 9 Connection Naming 4 Select the serial connection such as COM1 Figure 10 Serial port selection 5 Set the serial line to 2400 baud 8 data bits No parity 1 stop bit and no flow control Figure 11 Serial line configuration ...

Page 10: ...displayed as in Figure 15 If the password incorrect the correct password will be required as indicated below Password Error Please Enter Correct Password Figure 14 Password incorrect menu 1 5 2 Main menu In the main menu the user can choose between the six options indicated in Figure 15 and described in this section AS400 Relay Card 1 Function Segment Logic 2 Output Segment Function Configure 3 In...

Page 11: ...e for input signal logic settings To configure these segments select the segment number The selection menu from Figure 17 will be displayed Choose among the options open or close and type enter The menu will return to the function Segment Logic Menu Figure 16 Segment 1 Logic 1 Normal Open 2 Normal Close 0 Exit Please Enter Number Figure 17 Selection menu 1 5 2 2 Output Segment Function Configure m...

Page 12: ...ailure General Alarm Bypass Battery Low Over Load Warning 6 Battery Testing Battery Test is in progress 7 Shutdown Processing UPS executing shutdown after has received a shutdown command via communication port 8 Overload Warning UPS load is over the overload warning level defined in the specification of the UPS 9 UPS On The UPS is powered on and is capable of providing power to the system whether ...

Page 13: ...ally Close the UPS output will be disconnected If Signal is not active open Pin 8 Pin1 when Segment 6 is configured to Normal Open or close Pin 8 Pin1 when Segment 6 is configured to Normal Close the UPS will turn on 1 5 2 4 Function Segment Active Delay Time menu The Function Segment Active Delay Time and current settings value can be configured as follows Function Segment Active Delay Time 1 Seg...

Page 14: ...4 Default confirm menu 1 5 2 6 Firmware Version menu Firmware Version and development data is shown in this menu Firmware Version Firmware Version 00 05 2010 06 01 0 Exit Please Enter Number Figure 25 Firmware version menu 1 5 2 7 Exit menu The exit menu gives the user the option to save the configuration or leave the program without saving Exit 1 Exit and Save 2 Exit and Without Save 0 Not Exit P...

Reviews: