1.5.2.1 Function Segment Logic menu
The Function menu displays the Segment settings logic and current setting status.
-----------------------------------------------------------------------------
Function Segment Logic
-----------------------------------------------------------------------------
1. Segment 1 Logic, Current Setting (Normal Open)
2. Segment 2 Logic, Current Setting (Normal Open)
3. Segment 3 Logic, Current Setting (Normal Open)
4. Segment 4 Logic, Current Setting (Normal Open)
5. Segment 5 Logic, Current Setting (Normal Open)
6. Segment 6 Logic, Current Setting (Normal Open)
7. Segment 7 Logic, Current Setting (Normal Open)
8. Segment 8 Logic, Current Setting (Normal Open)
0. Exit
-----------------------------------------------------------------------------
Please Enter Number:
Figure 16: Logic Segment selection menu
Segments 1 to 5 are dedicated to output signal logic settings and Segments 6 to 8 are for input signal logic
settings. To configure these segments, select the segment number. The selection menu from Figure 17 will
be displayed. Choose among the options (open or close) and type enter. The menu will return to the function
Segment Logic Menu (Figure 16).
-----------------------------------------------------------------------------
Segment 1 Logic
-----------------------------------------------------------------------------
1. Normal Open
2. Normal Close
0. Exit
-----------------------------------------------------------------------------
Please Enter Number:
Figure 17: Selection menu
1.5.2.2 Output Segment Function Configure menu
The Output Segment Function is used to configure the current setting status of the output segment.
-----------------------------------------------------------------------------
Output Segment Function Configure
-----------------------------------------------------------------------------
1. Segment 1 function, Current Setting (Utility Failure)
2. Segment 2 function, Current Setting (Battery Low)
3. Segment 3 function, Current Setting (General Alarm)
4. Segment 4 function, Current Setting (Bypass Status)
5. Segment 5 function, Current Setting (Summary Alarm)
0. Exit
-----------------------------------------------------------------------------
Please Enter Number:
Figure 18: Output Segment selection menu
Selecting one of this segments, the user can configure its functionality as indicated in Figure 19.