12
ABB
ARC GUARD SYSTEM™ – TVOC-2-COM MODBUS CONFIGUR ATION MANUAL
2.1
General
Modbus/RTU is a 2-wire, RS485-based field bus
communication system for parameter value exchange.
INFORMATION
The implementation of the Modbus interface is
based on standards [1] and [2].
2.2
Modbus connector
The supplied Modbus connector has the following pin
configuration:
Table 1 Modbus Connector
Terminal
EIA/TIA-485 name
ITr/IDv
Description
+(B)
B/B’
D1
Transceiver terminal 1
Terminator 1 input*
-(A)
A/A’
D0
Transceiver terminal 0
Terminator 2 input*
DGND
C/C’
Common
Signal common
* If the device is connected as first or last device in a multi-drop system, a 120Ω terminator resistor should be installed between terminator inputs (A) and (B).
2.3
Modbus cables
Recommended cable: Belden 3105A (AWG22).
Figure 2
Modbus connector
+(B)
-(A) DGND
02
Draft, ne pas diffuser Wed Dec 05 2018 12:41:51 GMT+0100 (Romance Standard Time)
Summary of Contents for Arc Guard System TVOC-2-COM
Page 2: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 4: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 6: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 10: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 14: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 17: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 18: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 32: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 35: ...Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 38: ... Notes Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...
Page 39: ... Notes Draft ne pas diffuser Wed Dec 05 2018 12 41 51 GMT 0100 Romance Standard Time ...