Chapter 5 – Diagnostics
5-2
AC 80 User’s Manual
General Purpose LEDs
S0 to S7
When LED S7 is on, LEDs S0 to S6 display a status code (given in
Chapter 2).
When the special purpose LED F is on and S7 is off, an error code is
indicated by LEDs S0 to S6 as shown in the table below. The LEDs on
the left (S4 to S6) show the higher nibble of the error code, while those
on the right (S0 to S3) show the lower nibble.
Error indication examples:
Table 5-1 S0…S7 fault indications.
Code
(Hex)
Cause
Remedy
05
Bus error - memory
The processor tried to access a nonexistent memory location.
This indicates a serious system software error or defective
hardware.
Restart CPU and run application again. If error occurs again,
replace the CPU module PM820-2.
09
Stall alarm
This is a software problem and indicates that the CPU is not
working correctly. It is probably caused by a CPU overload.
Restart the system in STOP MODE.
Extend the cycle times of execution units in the PC program
or remove one or more execution units, e.g., control modules,
and load and deblock the application again.
0A
Memory test error
The error code appears during the RAM test, which is
performed during system initialization.
Replace the CPU module PM820-2.
0C
Instruction set fault
Replace the CPU module PM820-2
0D
Interval timer test failed
Replace the CPU module PM820-2.
0F
Bus error test failed
This is a hardware problem and indicates a CPU internal bus
error.
Replace the CPU module PM820-2.
22
START MODE selector in the STOP position
The START MODE selector on the PM820-2 DB element was
in STOP position when the system attempted to restart.
Restart the system with START MODE selector in either the
CLEAR or AUTO position.
27
Insufficient memory
The CPU could not start the application due to lack of
memory.
Restart the system in STOP MODE. Then remove all loaded
but unused options which may consume memory by loading
BASE software. Enable only necessary options and restart
the system by pressing the INIT push button with the START
MODE selector in CLEAR position.
42
Overload
The CPU was not able to run the specified control module.
The control module could not be completed within the
specified cycle time and was aborted.
Restart the system in STOP MODE. Then reduce the load by
extending the cycle times, for example, of control modules in
the PC program or remove one or more execution units, e.g.,
control modules. Load and deblock the application again.
B
F
R
S3
S2
S1
S5
S6
S7
S0
S4
T2
T1
P
05h (Bus error)
B
F
R
S3
S2
S1
S5
S6
S7
S0
S4
T2
T1
P
49h (Internal error)
Summary of Contents for Advant Controller 80
Page 1: ...ABB Drives User s Manual Advant Controller 80 ...
Page 2: ......
Page 4: ......
Page 10: ...vi AC 80 User s Manual ...
Page 34: ...Chapter 2 AC 80 Hardware and Connections 2 20 AC 80 User s Manual ...
Page 51: ...AC 80 User s Manual 4 13 Figure 4 8 The ACSRX PC element ...
Page 82: ...Chapter 5 Diagnostics 5 6 AC 80 User s Manual ...
Page 83: ......