Chapter 4 – Programming the AC 80
4-4
AC 80 User’s Manual
Configuration of
DB Elements for
ACS 600 Standard Drive
DB Elements
The ACS 600 Standard Drive requires two types of DB elements,
DRIDS and DRISTD.
The DRIDS DB element is used for the configuration of transmitted and
received datasets. Two DRIDS elements can be configured for one
Standard Drive.
Figure 4-1 DB element DRIDS for ACS 600 Standard Drive.
DRIDS has three terminals (I1, I2 and I3) for transmitting data to the
drive and three terminals (O1, O2 and O3) for receiving data from the
drive. The DS_NO terminal defines the datasets number selected for
transmit and receive. (One dataset includes three integers.) WR_ENA
must be set to 1 (by a connection from the PC section) to enable
dataset writing.