4-32
AC 80 User’s Manual
Essential Settings
Only the user-adjustable settings are represented. For more details,
see the
AC 80 PC Elements Reference Manual.
PM825
AF 100 part:
DSP
Base part:
Value references:
DAT
See the
AC 80 PC Elements Reference Manual.
CABLE
S (Single) or R (Redundant).
EN_DTMO
Enable Double Timeout:
NO; YES
TIMESYNC
Time Synchronisation:
NONE; MASTER; SLAVE
BUSNO
0
STNNO
1…79 (Must match AC 80 hardware address setting).
NAME
Unique dataset name (max. 20 characters).
ACT
0 = Spare element
1 = Active element
BUS
0
IDENT
Dataset identification (1…50). Must match the IDENT
terminal value in the corresponding PC element.
SOURCE
Direction of communication:
RECEIVE; SEND
STATION
AF 100 station number of the opposite target.
CYCLETIM
Transmission interval in milliseconds.
SORT_REF
Sort references:
NO; YES
REF1
User-definable name of a DAT element.
REF2
User-definable name of a DAT element.
• • •
• • •
REF8
User-definable name of a DAT element.