Picture
UDC- test point
STEP 2
Freewheeling diode measurement
Performance
Use a multimeter to make sure that the measurements for the output
freewheeling diodes are OK.
Pass criteria
By using the diode measurement setting for the multimeter, you should get
following values:
+ probe
- probe
R1-R5 display
U
+DC
~0,4 Vdc
V
+DC
~0,4 Vdc
W
+DC
~0,4 Vdc
+DC
U
OL
+DC
V
OL
+DC
W
OL
+ probe
- probe
R1-R5 display
U
-DC
OL
V
-DC
OL
W
-DC
OL
-DC
U
~0,4 Vdc
-DC
V
~0,4 Vdc
-DC
W
~0,4 Vdc
Meaning of this test
To ensure that the output freewheeling diodes are OK.