Parameters and firmware blocks
206
(3)
Last speed
Communication break detection active. Upon a communication break,
the drive generates alarm FIELDBUS COMM and freezes the speed
to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING
! Make sure that it is safe to continue operation in
case of a communication break.
50.03
COMM LOSS T OUT
(see above)
Defines the time delay before the action defined by parameter
is taken.
Time count starts when the link fails to update the message.
0.3…6553.5 s
Delay for fieldbus communication loss function.
50.04
FBA REF1 MODESEL
(see above)
Selects the fieldbus reference FBA REF1 scaling and the actual value, which is sent to the fieldbus
(FBA ACT1).
(0)
Raw data
No scaling (ie, data is transmitted without scaling). Source for the
actual value, which is sent to the fieldbus, is selected by parameter
.
(1)
Torque
Fieldbus adapter module uses torque reference scaling. Torque
reference scaling is defined by the used fieldbus profile (eg, with ABB
Drives Profile integer value 10000 corresponds to 100% torque
value). Signal
is sent to the fieldbus as an actual value.
See the
User’s Manual
of the appropriate fieldbus adapter module.
(2)
Speed
Fieldbus adapter module uses speed reference scaling. Speed
reference scaling is defined by the used fieldbus profile (eg, with ABB
Drives Profile integer value 20000 corresponds to the value of
parameter
). Signal
is sent
to the fieldbus as an actual value. See the
User’s Manual
of the
appropriate fieldbus adapter module.
(3)
Position
Fieldbus adapter module uses position reference scaling. Position
reference scaling is defined by parameters
and
. Signal
is sent to the fieldbus
as an actual value.
(4)
Velocity
Fieldbus adapter module uses position speed scaling. Position speed
scaling is defined by parameters
. Signal
is sent to the
fieldbus as an actual value.
(5)
Auto
One of the above selections is chosen automatically according to the
currently active control mode. See parameter group
.
50.05
FBA REF2 MODESEL
(see above)
Selects the fieldbus reference FBA REF2 scaling.
See parameter
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...