Parameters 435
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Direct axis inductance.
1 = 10 mH
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Quadrature axis inductance.
1 = 10 mH
Defines an angle offset between the zero position of the
synchronous motor and the zero position of the position
sensor.
This value is initially set by the autophasing routine when an
absolute encoder or an incremental encoder with Z-pulse is
used. The value can be fine-tuned by setting
Notes:
• The value is in electrical degrees. The electrical angle
equals the mechanical angle multiplied by the number of
motor pole pairs.
• This parameter is valid only for permanent magnet motors.
0 deg
0…360 deg
Angle offset.
1 = 1 deg
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
;
(
b1);
(
b2)
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Permanent magnet
motor
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal BackEMF
voltage.
1
SynRM
Synchronous reluctance motor. Three-phase AC synchronous
motor with salient pole rotor without permanent magnets.
2
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...