Operation principle and hardware description 33
Supply unit control devices
A supply unit is typically controlled using the local control devices installed on the cabinet
door. No additional control connections are needed. However, it is possible to:
•
control the supply unit through the control panel and fieldbus
•
read the status information of the supply unit through the control panel, fieldbus and
relay output
•
stop the supply unit with an externally wired emergency stop button (if the unit is
equipped with an emergency stop option).
The supply unit I/O control interface is in internal use. See section
on page
.
The data in brackets, for example [Q1], refer to the item designations in ABB example
circuit diagrams.
Main disconnector [Q1]
You must equip the supply unit with a main disconnector. You can use either a main
switch-disconnector [Q1.1] or a withdrawable main breaker [Q1].
Auxiliary voltage switch [Q21]
You can equip the supply unit with an auxiliary voltage switch [Q21]. Using the switch, you
can disconnect the auxiliary circuit from the power line.
Operating switch [S21]
You can equip the supply unit with the two-position operating switch [S21]. Connect the
switch to Run/Enable digital input of the control unit.
By default, the operating switch controls the unit as follows:
•
The Run/Enable position: The control program receives the Run/Enable command
through the digital input DI2. The control program closes the main contactor [Q2] or
main breaker with relay output RO3. The supply unit starts rectifying and charging the
DC link of the drive.
•
The Off position: The control program does not receive the Run/Enable command
through the digital input. The program opens the main contactor [Q2] or main breaker
with the relay output and the supply module stops rectifying.
For more information on the on/off control logic, see
ACS880 diode supply control program
firmware manual
(3AUA0000103295 [English]).
Emergency stop button [S61] and emergency stop reset
button [S62]
You can equip the supply unit with an emergency stop button [S61] and an emergency
stop reset button [S62].
Note:
The customer is fully responsible for implementing and testing the functional safety
circuits according to the relevant legislation and acceptance testing regulations. The
functional safety option manuals listed in section
on page
give
examples on implementing the safety circuits in ACS880 multidrives.
Summary of Contents for ACS880-304 +A018
Page 1: ...ABB industrial drives Hardware manual ACS880 304 A018 diode supply modules ...
Page 4: ......
Page 14: ...14 ...
Page 52: ...52 Cabinet construction Kits for 2 D7T 12 pulse Rittal TS 8 ...
Page 53: ...Cabinet construction 53 Stage 1 Installation of common parts ...
Page 54: ...54 Cabinet construction Stage 2 Module installation parts ...
Page 55: ...Cabinet construction 55 Stage 3 Module installation ...
Page 56: ...56 Cabinet construction Stage 4 AC busbars to the module ...
Page 57: ...Cabinet construction 57 Stage 5 DC busbars to the module ...
Page 58: ...58 Cabinet construction Stage 6 Shroud installation ...
Page 60: ...60 Cabinet construction Kits for 1 D8T 6 pulse Rittal TS 8 ...
Page 61: ...Cabinet construction 61 Stage 1 Installation of common parts ...
Page 62: ...62 Cabinet construction Stage 2 Module installation parts ...
Page 63: ...Cabinet construction 63 Stage 3 Quick connector installation ...
Page 64: ...64 Cabinet construction Stage 4 DC busbars to the module ...
Page 65: ...Cabinet construction 65 Stage 5 AC busbars to quick connector ...
Page 66: ...66 Cabinet construction Stage 6 AC busbar ...
Page 67: ...Cabinet construction 67 Stage 7 Module installation ...
Page 68: ...68 Cabinet construction Stage 8 Shroud installation ...
Page 70: ...70 Cabinet construction Kits for 1 D8T 6 pulse generic cabinet ...
Page 72: ...72 Cabinet construction Kits for 2 D8T 6 pulse Rittal TS 8 ...
Page 73: ...Cabinet construction 73 Stage 1 Installation of common parts ...
Page 74: ...74 Cabinet construction Stage 2 Module installation parts ...
Page 75: ...Cabinet construction 75 Stage 3 Quick connector installation ...
Page 76: ...76 Cabinet construction Stage 4 DC busbars ...
Page 77: ...Cabinet construction 77 Stage 5 AC busbars to quick connector ...
Page 78: ...78 Cabinet construction Stage 6 AC fuse busbars installation ...
Page 79: ...Cabinet construction 79 Stage 7 Module installation ...
Page 80: ...80 Cabinet construction Stage 8 Shroud installation ...
Page 82: ...82 Cabinet construction Kits for 2 D8T 6 and 12 pulse generic cabinet ...
Page 84: ...84 Cabinet construction Kits for 2 D8T 12 pulse Rittal TS 8 ...
Page 85: ...Cabinet construction 85 Stage 1 Installation of common parts ...
Page 86: ...86 Cabinet construction Stage 2 Module installation parts ...
Page 87: ...Cabinet construction 87 Stage 3 Quick connectors ...
Page 88: ...88 Cabinet construction Stage 4 DC busbar installation ...
Page 89: ...Cabinet construction 89 Stage 5 AC busbars to quick connector ...
Page 90: ...90 Cabinet construction Stage 6 AC busbars to main AC installation ...
Page 91: ...Cabinet construction 91 Stage 7 Module installation DC connection flanges ...
Page 92: ...92 Cabinet construction Stage 8 Shroud installation ...
Page 94: ...94 Cabinet construction Kits for 3 D8T 6 pulse generic cabinet ...
Page 118: ...118 Start up ...
Page 125: ...Maintenance 125 2 3 ...
Page 127: ...Maintenance 127 2 3 ...
Page 132: ...132 Maintenance 4 5 6 7 8 6 10 10 ...
Page 140: ...140 Maintenance 5 a c b 6 d e 9 ...
Page 144: ...144 Maintenance 6 b c 7 d 8 ...
Page 214: ...214 Ordering information ...
Page 240: ...240 Dimension drawings Dimensions of D7T supply module ...
Page 241: ...Dimension drawings 241 Dimensions of D8T supply module ...
Page 244: ...244 Dimension drawings Dimensions of BCU control unit ...
Page 257: ...Dimension drawings 257 Oval toroid kit ...
Page 258: ...258 Dimension drawings Oval toroid ...
Page 259: ...Dimension drawings 259 Dimensions of CVAR board UL CSA Dimensions in mm 1 mm 0 0394 in ...
Page 260: ...260 Dimension drawings ...
Page 280: ...www abb com drives www abb com drivespartners 3AXD50000010104 Rev C EN 2015 12 03 Contact us ...