232 Control unit
Default I/O connection diagram of the supply unit
XD2D
Drive-to-drive link
1
B
Drive-to-drive link (not in use by default)
2
A
3
BGND
4
Shield
X485
RS485 connection
5
B
Not in use (not in use by default)
6
A
7
BGND
8
Shield
XRO1…XRO3
Relay outputs
11
NC
XRO1:
Running
2)
(energized = running)
250 V AC / 30 V DC / 2 A
12
COM
13
NO
21
NC
XRO2:
Fault(-1)
2)
(Energized = no fault)
250 V AC / 30 V DC / 2 A
22
COM
23
NO
31
NC
XRO3:
MCB ctrl
1)
(Energized = closes main contactor/breaker)
250 V AC / 30 V DC / 2 A
32
COM
33
NO
XSTO, XSTO OUT XSTO connector
1
OUT
XSTO connector. Both circuits (power module, control unit) must be closed for
the supply unit to start. (IN1 and IN2 must be connected to OUT.)
8)
2
SGND
3
IN1
4
IN2
5
IN1
Not in use
6
SGND
7
IN2
8
SGND
XDI
Digital inputs
1
DI1
Temp fault
2)
(0 = overtemperature)
2
DI2
Run / enable
2)
(1 = run / enable)
3
DI3
MCB fb
1)
(0 = main contactor/breaker open)
4
DI4
Auxiliary circuit breaker fault
2)
5
DI5
Not in use by default. Can be used for eg, earth fault monitoring.
6
DI6
Reset
2)
(0 -> 1 = fault reset)
7
DIIL
Not in use by default. Can be used for eg, emergency stop.
XDIO
Digital input/outputs
1
DIO1
Not in use by default
2
DIO2
Not in use by default
3
DIOGND
Digital input/output ground
4
DIOGND
Digital input/output ground
XD24
Auxiliary voltage output
5
+24VD
+24 V DC 200 mA
6)
6
DICOM
Digital input ground
7
+24VD
+24 V DC 200 mA
6)
8
DIOGND
Digital input/output ground
DICOM=DIOGND
Ground selection switch
7)
XAI
Analog inputs, reference voltage output
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Not in use by default.
0(2)…10 V,
R
in
> 200 kohm
3)
5
AI1-
6
AI2+
Not in use by default.
0(4)…20 mA,
R
in
= 100 ohm
4)
7
AI2-
XAO
Analog outputs
1
AO1
Zero
2)
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Zero
2)
0…20 mA,
R
L
< 500 ohm
4
AGND
XPOW
External power input
1
+24VI
24 V DC, 2.05 A
2
GND
3
+24VI
4
GND
X12
Not in use in supply modules
X13
Control panel connection
X205
Memory unit connection
Summary of Contents for ACS880-304 +A018
Page 1: ...ABB industrial drives Hardware manual ACS880 304 A018 diode supply modules ...
Page 4: ......
Page 14: ...14 ...
Page 52: ...52 Cabinet construction Kits for 2 D7T 12 pulse Rittal TS 8 ...
Page 53: ...Cabinet construction 53 Stage 1 Installation of common parts ...
Page 54: ...54 Cabinet construction Stage 2 Module installation parts ...
Page 55: ...Cabinet construction 55 Stage 3 Module installation ...
Page 56: ...56 Cabinet construction Stage 4 AC busbars to the module ...
Page 57: ...Cabinet construction 57 Stage 5 DC busbars to the module ...
Page 58: ...58 Cabinet construction Stage 6 Shroud installation ...
Page 60: ...60 Cabinet construction Kits for 1 D8T 6 pulse Rittal TS 8 ...
Page 61: ...Cabinet construction 61 Stage 1 Installation of common parts ...
Page 62: ...62 Cabinet construction Stage 2 Module installation parts ...
Page 63: ...Cabinet construction 63 Stage 3 Quick connector installation ...
Page 64: ...64 Cabinet construction Stage 4 DC busbars to the module ...
Page 65: ...Cabinet construction 65 Stage 5 AC busbars to quick connector ...
Page 66: ...66 Cabinet construction Stage 6 AC busbar ...
Page 67: ...Cabinet construction 67 Stage 7 Module installation ...
Page 68: ...68 Cabinet construction Stage 8 Shroud installation ...
Page 70: ...70 Cabinet construction Kits for 1 D8T 6 pulse generic cabinet ...
Page 72: ...72 Cabinet construction Kits for 2 D8T 6 pulse Rittal TS 8 ...
Page 73: ...Cabinet construction 73 Stage 1 Installation of common parts ...
Page 74: ...74 Cabinet construction Stage 2 Module installation parts ...
Page 75: ...Cabinet construction 75 Stage 3 Quick connector installation ...
Page 76: ...76 Cabinet construction Stage 4 DC busbars ...
Page 77: ...Cabinet construction 77 Stage 5 AC busbars to quick connector ...
Page 78: ...78 Cabinet construction Stage 6 AC fuse busbars installation ...
Page 79: ...Cabinet construction 79 Stage 7 Module installation ...
Page 80: ...80 Cabinet construction Stage 8 Shroud installation ...
Page 82: ...82 Cabinet construction Kits for 2 D8T 6 and 12 pulse generic cabinet ...
Page 84: ...84 Cabinet construction Kits for 2 D8T 12 pulse Rittal TS 8 ...
Page 85: ...Cabinet construction 85 Stage 1 Installation of common parts ...
Page 86: ...86 Cabinet construction Stage 2 Module installation parts ...
Page 87: ...Cabinet construction 87 Stage 3 Quick connectors ...
Page 88: ...88 Cabinet construction Stage 4 DC busbar installation ...
Page 89: ...Cabinet construction 89 Stage 5 AC busbars to quick connector ...
Page 90: ...90 Cabinet construction Stage 6 AC busbars to main AC installation ...
Page 91: ...Cabinet construction 91 Stage 7 Module installation DC connection flanges ...
Page 92: ...92 Cabinet construction Stage 8 Shroud installation ...
Page 94: ...94 Cabinet construction Kits for 3 D8T 6 pulse generic cabinet ...
Page 118: ...118 Start up ...
Page 125: ...Maintenance 125 2 3 ...
Page 127: ...Maintenance 127 2 3 ...
Page 132: ...132 Maintenance 4 5 6 7 8 6 10 10 ...
Page 140: ...140 Maintenance 5 a c b 6 d e 9 ...
Page 144: ...144 Maintenance 6 b c 7 d 8 ...
Page 214: ...214 Ordering information ...
Page 240: ...240 Dimension drawings Dimensions of D7T supply module ...
Page 241: ...Dimension drawings 241 Dimensions of D8T supply module ...
Page 244: ...244 Dimension drawings Dimensions of BCU control unit ...
Page 257: ...Dimension drawings 257 Oval toroid kit ...
Page 258: ...258 Dimension drawings Oval toroid ...
Page 259: ...Dimension drawings 259 Dimensions of CVAR board UL CSA Dimensions in mm 1 mm 0 0394 in ...
Page 260: ...260 Dimension drawings ...
Page 280: ...www abb com drives www abb com drivespartners 3AXD50000010104 Rev C EN 2015 12 03 Contact us ...