Connector data
Connector pitch 5 mm, wire size 2.5 mm2
Power supply (XPOW)
24 V (±10%) DC, 2 A
External power input.
Connector pitch 5 mm, wire size 2.5 mm2
Relay outputs RO1…RO3
(XRO1…XRO3)
250 V AC / 30 V DC, 2 A
Protected by varistors
Connector pitch 5 mm, wire size 2.5 mm2
+24 V output (XD24:2 and XD24:4)
Total load capacity of these outputs is 4.8 W (200 mA /
24 V) minus the power taken by DIO1 and DIO2.
Connector pitch 5 mm, wire size 2.5 mm2
Digital inputs DI1…DI6
(XDI:1…XDI:6)
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in: 2.0 kohm
Input type: NPN/PNP (DI1…DI5), PNP (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
DI6 (XDI:6) can alternatively be used as an input for a PTC
sensor. "0" > 4 kohm, "1" < 1.5 kohm.
I
max: 15 mA (DI1…DI5), 5 mA (DI6)
Connector pitch 5 mm, wire size 2.5 mm2
Start interlock input DIIL (XD24:1)
24 V logic levels: "0" < 5 V, "1" > 15 V
R
in: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
Connector pitch 5 mm, wire size 2.5 mm2
Digital inputs/outputs DIO1 and
DIO2 (XDIO:1 and XDIO:2)
As inputs: 24 V logic levels: "0" < 5 V, "1" > 15 V.
R
in: 2.0
kohm. Filtering: 1 ms.
Input/output mode selection by
parameters.
As outputs: Total output current from +24VD is limited to
200 mA
DIO1 can be configured as a fre-
quency input (0…16 kHz with hard-
ware filtering of 4 microseconds) for
24 V level square wave signal (sinus-
oidal or other wave form cannot be
used). DIO2 can be configured as
a 24 V level square wave frequency
output. See the firmware manual,
parameter group 111/11.
R
L
DIOx
DIOGND
+24VD
Connector pitch 5 mm, wire size 2.5 mm2
Reference voltage for analog inputs
+VREF and -VREF
(XAI:1 and XAI:2)
10 V ±1% and –10 V ±1%,
R
load 1…10 kohm
Maximum output current: 10 mA
136 Control units of the drive
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...