Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
Max. 95%
Max. 95%
Max. 95%
Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
IEC 60721-3-2:1997
IEC 60721-3-1:1997
IEC/EN 60721-3-3:2002:
Classification of environ-
mental conditions - Part 3-
3: Classification of groups
of environmental paramet-
ers and their severities -
Stationary use of weather
protected locations
Contamination
Chemical gases: Class
2C2
Solid particles: Class 2S2
Chemical gases: Class
1C2
Solid particles: Class 1S3
(packing must support this,
otherwise 1S2)
Chemical gases: Class
3C2
Solid particles: Class 3S2
(3S1 with IP20). No con-
ductive dust allowed.
IEC/EN 60721-3-2:1997
IEC/EN 60721-3-1:1997
IEC/EN 60721-3-3:2002
Vibration
2…9 Hz: max. 3.5 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
10…57 Hz: max. 0.075 mm
amplitude
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 Envir-
onmental testing Part 2:
Tests –Test Fc: Vibration
(sinusoidal)
9…200 Hz: 10 m/s
2
(32.8 ft/s
2
)
57…150 Hz: 1
g
57…150 Hz: 1
g
Units with marine construc-
tion (C121): Max.
1 mm (0.04 in.)
(5 … 13.2 Hz), max. 0.7
g
(13.2 … 100 Hz) sinusoidal
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
With packing max.
100 m/s
2
(328 ft/s
2
) 11 ms
Not allowed
Shock
IEC 60068-2-27:2008, EN
60068-2-27:2009
Environmental testing -
Part 2-27: Tests - Test Ea
and guidance: Shock
Technical data 77
Summary of Contents for ACS880-0500-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 607 3 phase brake units Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 54: ...54 ...
Page 62: ...62 ...
Page 66: ...66 Maintenance ...
Page 82: ...Dimension drawing bottom exit 82 Dimension drawings ...
Page 83: ...Dimension drawings 83 ...
Page 84: ...Dimension drawing top exit 84 Dimension drawings ...
Page 85: ... Dimension drawings 85 ...
Page 86: ......