Technical data 41
Power correction factor (k)
The tables below shows the power correction factor (k) for calculating the sum rectifying
capacity of the drives connected to the AC power line. Choose the lowest k factor of the
possible choices.
The tables also show the combinations of drives that you may connect to the AC power
line. Connect only the drives visible in the same table. Connect only combinations which
are visible in the same table and which are not marked as prohibited. The other
combinations are not allowed.
Example for choosing the k:
If you connect frames R5, R4 and R2 to the AC power line, possible values for k are:
•
0.7 for combination of frames R5 and R4
•
0.8 for combination of frames R5 and R2
•
0.8 for combination of frames R4 and R2.
Choose the smallest value (0.7) and use it in the calculations.
Frames R1 to R5
Frames R5 to R9
U
ac
= 208…240, 380…415, 380…500
U
ac
= 600…690
R5a: ACS880-01 types -07A3-7, -09A8-7, -14A2-7 and -018A-7.
R5b: ACS880-01 types -022A-7, -026A-7, -035A-7, -042A-7 and -049A-7.
The smaller drive may not be connected to the AC power line.
Frame
R1
R2
R3
R4
R5
R1
0.9
0.4
0.9
R2
0.4
0.9
0.7
0.8
0.8
R3
0.9
0.7
0.9
0.6
0.4
R4
0.8
0.6
0.9
0.7
R5
0.8
0.4
0.7
0.9
Frame
R5
R6
R7
R8
R9
R5
0.9
0.3
R6
0.3
0.9
0.9
0.5
0.3
R7
0.9
0.9
0.7
0.6
R8
0.5
0.7
0.9
0.9
R9
0.3
0.6
0.9
0.9
Frame
R5a
R5b
R6
R7
R8
R9
R5a
0.9
0.9
1
1
0.7
0.9
R5b
0.9
0.9
0.7
0.5
0.2
R6
1
0.7
0.9
1
0.8
0.7
R7
1
0.5
1
0.9
0.9
0.8
R8
0.7
0.2
0.8
0.9
0.9
1
R9
0.4
0.7
0.8
1
0.9
Summary of Contents for ACS880-04 drive modules
Page 4: ......
Page 10: ...10 Introduction to the manual...
Page 16: ...16 Operation principle and hardware description...
Page 30: ...30 Planning basics...
Page 38: ...38 Planning additional instructions...
Page 48: ...Contact us www abb com drives www abb com drivespartners 3AUA0000127818 Rev B EN 2014 04 17...