20 Planning – basics
Symbol
Name
Information
P
mot
Motoring power
Power that the motors take from the common DC link
P
mot,ave
Average motoring
power
Average power that the motors take from the common DC link. See the
duty cycle diagram of the common DC link.
Note:
For long cycles
times, define
P
mot,ave
over the worst-case 3 minutes time window.
P
mot,max
Maximum motoring
power
Maximum power that the motors take from the common DC link. See
the duty cycle diagram of the common DC link.
P
gen
Generating power
Power that the motors supply to the common DC link
P
gen,ave
Average
generating
power
Average power that the motors feed to the common DC link when they
are in generating mode (braking the load). See the duty cycle diagram
of the common DC link.
Note:
If you will use the brake choppers of the
drives in the system, determine
P
gen,ave
over the worst-case 30
seconds time window.
P
gen,max
Maximum
generating power
Maximum power that the motors feed to the common DC link when they
are in generating mode (braking the load). See the duty cycle diagram
of the common DC link.
P
rec
Rectifier power
Power that the drive input bridges (rectifiers) feed to the common DC
link. See section
Selecting the drives which are connected to
for the calculation instructions.
P
rec,ave
Average rectifier
power capacity
The drives that are connected to the AC power line can feed this
average power to the common DC link.
P
rec,max
Maximum rectifier
power capacity
The drives that are connected to the AC power line can feed this power
to the common DC link at the maximum.
P
br
Braking power
Surplus power that the brake resistors take from the common DC link.
(Alternatively: Power that the drive feeds to the AC power line if a
regenerative type of drive is in use.) See section
on page
P
br,cont
Continuous braking
power
Continuous braking power that the brake resistors take from the
common DC link. The braking is continuous if the braking time exceeds
30 seconds.
P
br,max
Maximum braking
power
Maximum braking power that the brake resistors take from the common
DC link. Brake choppers withstand this braking power for 5 second
within every minute.
Summary of Contents for ACS880-04 drive modules
Page 4: ......
Page 10: ...10 Introduction to the manual...
Page 16: ...16 Operation principle and hardware description...
Page 30: ...30 Planning basics...
Page 38: ...38 Planning additional instructions...
Page 48: ...Contact us www abb com drives www abb com drivespartners 3AUA0000127818 Rev B EN 2014 04 17...