584 Fault tracing
A8BF
ULC underload
warning
Programmable fault:
Selected signal has fallen
below the user underload
curve.
Check for any operating conditions
decreasing the monitored signal (for
example, loss of load if the torque or
current is being monitored).
Check the definition of the load curve
(parameter group
A8C0
Fan service counter
A cooling fan has reached the
end of its estimated lifetime.
See parameters
.
Check the auxiliary code. The code
indicates which fan is to be replaced.
0: Main cooling fan
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
A981
External warning 1
(Editable message text)
Programmable warning:
Fault in external device 1.
Check the external device.
Check setting of parameter
.
A982
External warning 2
(Editable message text)
Programmable warning:
Fault in external device 2.
Check the external device.
Check setting of parameter
.
A983
External warning 3
(Editable message text)
Programmable warning:
Fault in external device 3.
Check the external device.
Check setting of parameter
.
A984
External warning 4
(Editable message text)
Programmable warning:
Fault in external device 4.
Check the external device.
Check setting of parameter
.
A985
External warning 5
(Editable message text)
Programmable warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
AF80
INU-LSU comm loss
Programmable warning:
DDCS (fiber optic)
communication between
converters (for example, the
inverter unit and the supply
unit) is lost.
Note that the inverter unit will
continue operating based on
the status information that was
last received from the other
converter.
Check status of other converter
(parameters
).
Check settings of parameter group
. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...