Parameters 173
Selects a binary source whose status is transmitted as bit 13
of
.
False
0.
0
True
1.
1
). -
Selects a binary source whose status is transmitted as bit 14
of
.
False
0.
0
True
1.
1
). -
(Only visible when supply unit control activated by
Shows the status of the supply unit.
See also section
Control of a supply unit (LSU)
(page
and parameter group
This parameter is read-only.
-
0000h…FFFFh
Supply unit status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Ready on
1 = Ready to switch on
1
Ready run
1 = Ready to operate, DC link charged
2
Ready ref
1 = Operation enabled
3
Tripped
1 = A fault is active
4…6
Reserved
7
Warning
1 = A warning is active
8
Modulating
1 = The supply unit is modulating
9
Remote
1 = Remote control (EXT1 or EXT2)
0 = Local control
10
Net ok
1 = Supply network voltage OK
11…12 Reserved
13
Charging or
ready run
1 = Bit 1 or bit 14 active
14
Charging
1 = Charging contactor closed
0 = Charging contactor open
15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...