![ABB ACS880-01 Series Firmware Instructions Download Page 165](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621165.webp)
Parameters 165
Displays the age of the auxiliary cooling fan as a percentage
of its estimated lifetime. The estimate is based on the duty,
operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning (
) is generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…150%
Auxiliary cooling fan age.
1 = 1%
(Only visible when IGBT supply unit control activated by
Estimated supply unit temperature in percent of fault limit.
0.0% = 0 °C (32 °F)
94% approx. = Warning limit
100.0% = Fault limit
-
-40.0 … 160.0%
Supply unit temperature in percent.
1 = 1%
(Only visible when IGBT supply unit control activated by
Counts the closures of the main circuit breaker of the supply
unit.
-
0…4294967295
Count of closures of main circuit breaker.
1 = 1
06
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such
as digital inputs, the fieldbus interfaces and the application
program).
The bit assignments of the word are as described on page
. The related status word and state diagram are presented
respectively.
Note:
Bits 12…15 can be used to carry additional control
data, and used as a signal source by any binary-source
selector parameter.
This parameter is read-only.
-
0000h…FFFFh
Main control word.
1 = 1
The drive control word received from the application program
(if any). The bit assignments are described on page
.
This parameter is read-only.
-
0000h…FFFFh
Application program control word.
1 = 1
FBA A transparent
control word
Displays the unaltered control word received from the PLC
through fieldbus adapter A when a transparent
communication profile is selected eg. by parameter group
. See section
(page
).
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Control word received through fieldbus adapter A.
-
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...