Parameters 117
16.11
User IO sel lo
When parameter
is set to
, selects
the user parameter set together with parameter
. The status of the source defined by this parameter and
parameter
select the user parameter set as follows:
Const
Bit pointer setting (see
on page
). -
Pointer
16.12
User IO sel hi
See parameter
.
Const
Bit pointer setting (see
on page
). -
Pointer
16.14
Reset ChgParLog
Resets the log of latest parameter changes.
Done
Reset not requested (normal operation).
0
Reset
Reset log of latest parameter changes. The value reverts
automatically to
1
16.15
Menu set sel
Loads a short, long or custom parameter list. By default, short
parameter list is displayed by drive.
No request
No change has been requested.
0
Load short
Load short parameter list. Only a selective list of parameters
will be displayed.
1
Load long
Load long parameter list. All parameters will be displayed.
2
16.16
Menu set active
Shows which parameter list is active. See parameter
None
No parameter list is active.
0
Short menu
Short parameter list is active.
1
Long menu
Long parameter list is active. All parameters are displayed.
2
16.17
Power unit
Selects the unit of power for parameters such as
,
.
kW
Kilowatt.
0
hp
Horsepower.
1
19
19 Speed calculation
Speed feedback, speed window, etc. settings.
19.01
Speed scaling
Defines the terminal speed value used in acceleration and the
initial speed value used in deceleration (see parameter group
). Also defines the rpm value that
corresponds to 20000 for fieldbus communication with ABB
Drives communication profile.
0 … 30000 rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
19.02
Speed fb sel
Selects the speed feedback value used in control.
Estimated
A calculated speed estimate is used.
0
No.
Name/Value
Description
FbEq
Status of source
defined by par.
Status of source
defined by par.
User parameter
set selected
FALSE
FALSE
Set 1
TRUE
FALSE
Set 2
FALSE
TRUE
Set 3
TRUE
TRUE
Set 4