3BHS842007 E01 REV C
ACS6080
USER MANUAL
219/238
09 PREVENTIVE AND CORRECTIVE MAINTENANCE
9.4.15
Testing and replacing
auxiliary fan units
• Inspection intervals:
see the "ACS6080 preventive maintenance
• Service during operation:
possible
• Location:
• installed behind the doors of the following cabinets:
- COU cabinet (2 fan units)
- WCU cabinet (2 fan units in WCU and 2 fan units in the
optional REB)
- Water-cooled EXU cabinet
9.4.15.1 Testing auxiliary fan units
To switch the fan units on and off for the test, use the thermostats of the
fan units.
Procedure
1.
Switch on the auxiliary voltage for the fan unit to be tested.
2.
Take note the setting of the thermostat.
The factory-set value is also stated on the
Settings
label. The label is
attached to the inside of the cabinet door.
3.
To switch on a fan unit, turn the dial of the thermostat from the
factory-set value to a low value.
4.
Check that the fans run smoothly and if a fan is faulty, replace the
complete fan unit.
5.
Set the thermostat to the factory-set value.
Thermostat location
Identification
Factory-set value
COU
B2981
45° C
WCU
B5741
45° C