244 Parameters
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
WARNING!
Before you activate the function, make
sure that no dangerous situations can occur. The
function restarts the drive automatically and continues
operation after a fault.
The bits of this binary number correspond to the following
faults:
0000h
0000h…FFFFh
Automatic reset configuration word.
1 = 1
Defines the fault that can be automatically reset using
parameter
, bit 10.
0000h
0000h…FFFFh
Fault code.
10 = 1
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
.
0
0…5
Number of automatic resets.
10 = 1
Defines the time the automatic reset function will attempt to
reset the drive. During this time, it will perform the number of
automatic resets defined by
.
30.0 s
1.0…600.0 s
Time for automatic resets.
10 = 1 s
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
0.0 s
0.0…120.0 s
Autoreset delay.
10 = 1 s
Selects how the drive reacts when a motor phase loss is
detected.
No action
No action taken.
0
Fault
1
Selects how the drive reacts when an earth (ground) fault or
current unbalance is detected in the motor or the motor cable.
No action
No action taken.
0
Warning
The drive generates an
warning.
1
No.
Name/Value
Description
Def/FbEq16
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI supervision fault
4…9
Reserved
10
Selectable fault (see parameter
)
11
External fault 1 (from source selected by parameter
12
External fault 2 (from source selected by parameter
13
External fault 3 (from source selected by parameter
14
External fault 4 (from source selected by parameter
15
External fault 5 (from source selected by parameter