Note: Circuit breakers must not be used without fuses in UL installations.
Tested circuit breakers
You can use the circuit breakers listed in the technical data. Other circuit breakers can
be used with the drive if they provide the same electrical characteristics. ABB does
not assume any liability whatsoever for the correct function and protection with circuit
breakers not listed. Furthermore, if the recommendations given by ABB are not obeyed,
the drive can experience problems that the warranty does not cover.
■
Protecting the drive against thermal overload
The drive has overload protection as standard.
■
Protecting the input power cable against thermal overload
The drive has overload protection as standard. If the sizing of the input power cable
is correct, the drive overload protection protects also the cable against overload. In
case of parallel input power cables, it may be necessary to protect each cable
separately. Obey the local regulations.
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the
unit against ground faults in the motor and motor cable. This function is not a
personnel safety or a fire protection feature. See the firmware manual for more
information.
■
Residual current device compatibility
The drive is suitable for use with residual current devices of Type B.
Note: As standard, the drive contains capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause nuisance faults in residual current devices.
Implementing the emergency stop function
For safety reasons, install the emergency stop devices at each operator control station
and at other operating stations where the emergency stop may be needed. Implement
the emergency stop according to relevant standards.
Note: You can use the Safe torque off function of the drive to implement the Emergency
stop function.
Implementing the Safe torque off function
See
The Safe torque off function (page 221)
Implementing the power loss ride-through function
If the incoming supply voltage is cut off, the drive will continue to operate by utilizing
the kinetic energy of the rotating motor. The drive will be fully operational as long as
the motor rotates and generates energy to the drive.
Guidelines for planning the electrical installation 93
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...