![ABB ACS580-04 Hardware Manual Download Page 116](http://html.mh-extra.com/html/abb/acs580-04/acs580-04_hardware-manual_2579116.webp)
Task (motor cables)
Step
Connect the phase T2/V2 conductors to the T2/V2 connection terminal.
7
Install the T1/U2 connection terminal to the insulators. See the warning in step 4.
8
Connect the phase T1/U2 conductors to the T1/U2 terminal.
9
Remove the plastic sheeting from the output clear plastic shroud from both sides.
10
Install the shroud to the drive module.
11
Install the lower front cover to the drive module.
12
Task (input cables)
Step
Ground the input cable shields (if present) 360° at the cabinet entry.
1
Connect the twisted shields of the input cables and separate ground cable (if present) to the
cabinet grounding busbar.
2
Step drill carefully sufficiently big holes to the lead-through clear plastic shroud for the cables
to the connected. Align the holes in the vertical direction according to the alignment holes in
the shroud. Smooth the hole edges.
3
Remove the plastic sheeting from both sides of the shroud.
Attach the cables firmly to the cabinet frame to prevent chafing against the hole edges.
Put the conductors of the input cables through the drilled holes in the clear plastic shroud.
4
For drive modules without H370: Connect the input cable conductors to the drive
module L1/U1, L2/V1 and L3/W1 connection busbars, Go to step 12.
5
For H370: Perform steps 6 to 11.
Screw in and tighten the insulators to the drive module by hand. Install the L1/U1 connection
terminal to the insulators.
6
WARNING!
Do not use longer screws or a larger tightening torque than specified in the in-
stallation drawing. They can damage the insulator and cause a dangerous voltage
to be present at the module frame.
Connect the L1/U1 conductors to the L1/U1 connection terminal.
7
Install the L2/V1 connection terminal to the insulators. See the warning in step 5.
8
Connect the L2/V1 conductors to the L2/V1 connection terminal.
9
Install the L3/W1 connection terminal to the insulators. See the warning in step 5.
10
Connect the L3/W1 conductors to the L3/W1 connection terminal.
11
Install the lead-through clear plastic shroud. Install the front clear plastic shroud and upper
front cover. Remove the cardboard protective covering from the drive module air outlet.
12
Install the side and top clear plastic shrouds to the drive module.
13
116 Installation example of drive module with IP20 shrouds (B051)
Summary of Contents for ACS580-04
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 60: ...60 ...
Page 69: ...2 1 Tapping screw M6 12 Torx T30 Hex 9 N m 6 6 lbf ft Mechanical installation 69 10 ...
Page 72: ...72 ...
Page 100: ...100 ...
Page 120: ...120 ...
Page 128: ...2 7a 7b 5 3 3 7a 7b 8a 8b 8b 4 128 Installation example with full cabling panels option H381 ...
Page 133: ...Installation example with full cabling panels option H381 133 ...
Page 134: ...134 ...
Page 146: ...146 ...
Page 157: ...External control unit option P906 157 ...
Page 162: ...162 ...
Page 164: ...164 ...
Page 200: ...R10 standard configuration 200 Dimension drawings ...
Page 201: ...R10 with options E208 0H354 H356 H370 0H371 Dimension drawings 201 ...
Page 202: ...R10 with option B051 202 Dimension drawings ...
Page 203: ...R10 with options E208 H356 P906 Dimension drawings 203 ...
Page 204: ...R10 with options E208 0H371 H356 0H354 H370 P906 204 Dimension drawings ...
Page 205: ...R10 with options B051 P906 Dimension drawings 205 ...
Page 208: ...R11 standard configuration 208 Dimension drawings ...
Page 209: ...R11 with options E208 0H371 H356 0H354 H370 Dimension drawings 209 ...
Page 210: ...R11 with option B051 210 Dimension drawings ...
Page 211: ...R11 with options E208 H356 P906 Dimension drawings 211 ...
Page 212: ...R11 with options E208 0H371 H356 0H354 H370 P906 212 Dimension drawings ...
Page 213: ...R11 with options B051 P906 Dimension drawings 213 ...
Page 248: ...248 ...
Page 260: ...260 ...
Page 265: ...CHDI 01 115 230 V digital input extension module 265 ...
Page 266: ...266 ...
Page 272: ...272 CMOD 01 multifunction extension module external 24 V AC DC and digital I O ...
Page 278: ...278 ...
Page 280: ...280 ...