Program features 89
Motor overload protection requires that you specify a motor current tripping level. This
is defined by a curve using parameters
,
and
. The tripping level is
the motor current at which the overload protection will ultimately trip if the motor
current remains at this level continuously.
The motor overload class (class of operation), parameter
,
is given as the time required for the overload relay to trip when operating at 7.2 times
the tripping level in the case of IEC 60947-4-1 and 6 times the tripping level in the
case of NEMA ICS 2. The standards also specify the time to trip for current levels
between the tripping level and the 6 times tripping level. The drive satisfies the IEC
standard and NEMA standard trip times.
Using class 20 satisfies the UL 508C requirements.
The motor overload algorithm monitors the squared ratio (motor current / tripping
level)2 and accumulates this over time. This is sometimes to as I2t protection. The
accumulated value is shown with parameter
.
that when
reaches 88%, a motor overload
warning will be generated, and when it reaches 100%, the drive will trip on the motor
overload fault. The rate at which this internal value is increased depends on the
actual current, tripping level current and overload class selected.
Parameters
,
serve a dual purpose. They determine the load
curve for temperature estimate as well as specify the overload tripping level.
Settings and diagnostics
Parameters common to motor thermal protection and motor overload protection:
...
(page
).
Parameters specific to motor overload protection:
(page
...
(page
).
(page
(page
).
Programmable protection functions
External events (parameters
…
)
Five different event signals from the process can be connected to selectable inputs to
generate trips and warnings for the driven equipment. When the signal is lost, an
external event (fault, warning, or a mere log entry) is generated.
Motor phase loss detection (parameter
The parameter selects how the drive reacts whenever a motor phase loss is detected.
The motor phase loss detection is enabled by default and displays fault
whenever the drive detects a phase loss. The motor phase loss detection
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...