ACS550 User’s Manual
239
Fieldbus adapter
Actual Value
As described earlier in section
on page
, Actual Values are
words containing drive values.
Actual Value scaling
The scaling of the integers sent to the fieldbus as Actual Values depends on the
resolution of the selected drive parameter. Except as noted for
ACT
1 and
ACT
2 below,
scale the feedback integer using the resolution listed for the parameter in section
on page
. For example:
Data words 5 and 6 are scaled as follows:
Virtual addresses of the drive control
The virtual address area of the drive control is allocated as follows:
Feedback integer
Parameter resolution
Scaled Value
1
0.1 mA
1 · 0.1 mA = 0.1 mA
10
0.1%
10 · 0.1% = 1%
ABB Drives profile
Contents
Scaling
ACT
1
ACTUAL
SPEED
-20000 … +20000 = -(par. 1105) … +(par. 1105)
ACT
2
TORQUE
-10000 … +10000 = -100% … +100%
1
Control Word
2
Reference 1 (REF
1)
3
Reference 2 (REF
2)
4
Status Word
5
Actual Value 1 (ACT
1)
6
Actual Value 2 (ACT
2)