The following table lists all parameters. Table header abbreviations are:
• S
=
Parameters can be modified only when the drive is stopped.
• User = Space to enter desired parameter values.
Some values depend on the “construction” as indicated in the table by “01:” or “U1:”.
Refer to the type code on the drive, for example ACS550-
01
..
Code
Name
Range
Resolution
Default
User S
Group 99: START-UP DATA
9901
LANGUAGE
0…15 / 0…3
1
0 (
ENGLISH
)
9902
APPLIC
MACRO
-3…8, 31
1
1 (
ABB
STANDARD
)
!
9904
MOTOR
CTRL
MODE
1 =
VECTOR
:
SPEED
, 2 =
VECTOR
:
TORQUE
,
3 =
SCALAR
:
FREQ
1
3 (
SCALAR
:
FREQ
)
!
9905
MOTOR
NOM
VOLT
115…345 V
1 V
230 V
!
01: 200…600 V /
U1: 230…690 V
1 V
01: 400 V /
U1: 460 V
!
U1: 288…862 V
1 V
U1: 575 V
!
9906
MOTOR
NOM
CURR
0.2 ·
I
2hd
… 2.0 ·
I
2hd
0.1 A
1.0 ·
I
2hd
!
9907
MOTOR
NOM
FREQ
10.0.0…500.0 Hz
0.1 Hz
01: 50.0 Hz /
U1: 60.0 Hz
!
9908
MOTOR
NOM
SPEED
50…30000 rpm
1 rpm
Size dependent
!
9909
MOTOR
NOM
POWER
0.2…3.0 ·
P
hd
01: 0.1 kW /
U1: 0.1 hp
1.0 ·
P
hd
!
9910
ID
RUN
0 =
OFF
/
IDMAGN
, 1 =
ON
1
0 (
OFF
/
IDMAGN
)
!
Group 01: OPERATING DATA
0101
SPEED
&
DIR
-30000…30000 rpm
1 rpm
-
0102
SPEED
0…30000 rpm
1 rpm
-
0103
OUTPUT
FREQ
0.0…500.0 Hz
0.1 Hz
-
0104
CURRENT
0.0…2.0 ·
I
2hd
0.1 A
-
0105
TORQUE
-200.0…200.0%
0.1%
-
0106
POWER
-2.0…2.0 ·
P
hd
0.1 kW
-
0107
DC
BUS
VOLTAGE
0…2.5 · V
dN
1 V
-
0109
OUTPUT
VOLTAGE
0…2.0 · V
dN
1 V
-
0110
DRIVE
TEMP
0.0…150.0
°
C
0.1
°
C
-
0111
EXTERNAL
REF
1
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz -
0112
EXTERNAL
REF
2
0.0…100.0% (0.0…600.0% for torque) 0.1%
-
0113
CTRL
LOCATION
0 =
LOCAL
, 1 =
EXT
1, 2 =
EXT
2
1
-
0114
RUN
TIME
(
R
)
0…9999 h
1 h
0 h
0115
KWH
COUNTER
(
R
)
0…9999 kWh
1 kWh
-
0116
APPL
BLK
OUTPUT
0.0…100.0% (0.0…600.0% for torque) 0.1%
-
0118
DI
1-3
STATUS
000…111 (0…7 decimal)
1
-
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...