18
ACS550 User’s Manual
Installation
Wiring overview
Conduit/Gland kit
Wiring drives with the IP21 / UL type 1 enclosure requires a conduit/gland kit with the
following items:
• conduit/gland box
• five (5) cable clamps (ACS550-01 only)
• screws
• cover.
The kit is included with IP21 / UL type 1 enclosures.
Wiring requirements
WARNING!
Ensure the motor is compatible for use with the ACS550. The drive must
be installed by a competent person in accordance with the considerations defined in
section
. If in doubt, contact your local ABB
sales or service office.
As you install the wiring, observe the following:
• There are four sets of wiring instructions – one set for each combination of drive
enclosure type (IP21 / UL type and IP54 / UL type 12) and wiring type (conduit or
cable). Be sure to select the appropriate procedure.
• Determine electro-magnetic compliance (EMC) requirements per local codes.
See section
Motor cable requirements for CE & C-Tick compliance
.
In general:
– Follow local codes for cable size.
– Keep these four classes of wiring separated: input power wiring, motor wiring,
control/communications wiring and braking unit wiring.
• When installing input power and motor wiring, refer to the following, as
appropriate:
• To locate input power and motor connection terminals, see section
on page
. For specifications on power terminals, see
section
Drive’s power connection terminals
on page
.
• For corner grounded TN systems, see section
on
page
• For IT systems, see section
on page
.
Terminal
Description
Specifications and notes
U1, V1, W1
1
3-phase power supply input
PE
Protective Ground
on page
U2, V2, W2
Power output to motor
1
The ACS550 -x1-xxxx-2 (208…240 V series) can be used with a single phase supply, if output
current is derated by 50%. For single phase supply voltage, connect power at U1 and W1.
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...