Grounding and routing
Motor cable shielding
Motor cables require shielding using conduit, armored cable or shielded cable.
• Conduit – When using conduit:
– Bridge joints with a ground conductor bonded to the conduit on each side of
the joint.
– Bond conduit run to the drive enclosure.
– Use a separate conduit run for motor cables (also separate input power and
control cables).
– Use a separate conduit run for each drive.
• Armored cable – When using armored cable:
– Use six-conductor (3 phases and 3 grounds), type MC continuous corrugated
aluminium armor cable with symmetrical grounds.
– Armored motor cable can share a cable tray with input power cables, but not
with control cables.
• Shielded cable – For shielded cable details, see section
requirements for CE & C-Tick compliance
on page
Grounding
See section
on page
For CE compliant installations and installations where EMC emissions must be
minimized, see section
.
Drive’s motor connection terminals
The drive’s motor and input power terminals have the same specifications. See
section
Drive’s power connection terminals
on page
.
Motor cable requirements for CE & C-Tick compliance
The requirements in this section apply for CE or C-Tick compliance.
Minimum requirement (CE & C-Tick)
The motor cable must be a symmetrical three conductor cable with a concentric PE
conductor or a four conductor cable with a concentric shield, however, a symmetrical
constructed PE conductor is always recommended. The following figure shows the
minimum requirement for the motor cable screen (for example, MCMK, NK Cables).
Insulation jacket
Copper wire screen
Cable core
Inner insulation
Summary of Contents for ACS550 Series
Page 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 User s Manual Table of contents ...
Page 84: ...84 ACS550 User s Manual Application macros ...
Page 188: ...188 ACS550 User s Manual Parameters ...
Page 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Page 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...