ACS2000 User manual
2UEA001270 Rev. F
6-5 (16)
Chapter 6 - Electrical installation
Table 6-1
Control cable requirements
6.4
Cable entry
6.4.1
TEU (Terminal Entry Unit) for power cables and ground cable
The TEU for the power cables and the ground cable of the drive allows for
either top or bottom cable entry.
The unused cable entry is closed by a cover (6).
Figure 6-2
Terminal entry unit
Signal type
General cable type
Cross-section
Analog in
Twisted pair(s) - Overall shield
0.5 to 2.5 mm
2
/ 20 to 12 AWG
Analog out
Twisted pair(s) - Overall shield
0.5 to 2.5 mm
2
/ 20 to 12 AWG
Digital in
Twisted pair(s) - Overall shield
0.5 to 2.5 mm
2
/ 20 to 12 AWG
Digital out
Twisted pair(s) - Overall shield
0.5 to 2.5 mm
2
/ 20 to 12 AWG
Pulse
encoder
Twisted pair cable with separately
shielded pairs and overall shield
0.5 mm
2
/ 4 x (2+1) /
20 to 18 AWG
Legend
1
PE ground
bus
2
Power IN
terminals
3
Motor OUT
terminals
4
Strain relief
5
Cable entry
cover
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......