Fieldbus control
250
03.01 MAIN CONTROL WORD
The upper case boldface text refers to the states shown in the
ABB Drives communication profile
Bit
Name
Value Enter STATE/Description
0
OFF1 CONTROL 1
Enter
READY TO OPERATE.
0
Stop along currently active deceleration ramp (22.03/22.05). Enter
OFF1 ACTIVE;
proceed to
READY TO SWITCH ON
unless other interlocks (OFF2, OFF3) are active.
1
OFF2 CONTROL 1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Enter
OFF2 ACTIVE
; proceed to
SWITCH-ON INHIBITED.
2
OFF3 CONTROL 1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined with Par.
. Enter
OFF3 ACTIVE
;
proceed to
SWITCH-ON INHIBITED.
Warning:
Ensure motor and driven machine can be stopped using this stop mode.
3
INHIBIT_
OPERATION
1
Enter OPERATION ENABLED. (Note: The Run Enable signal must be active; see
parameter
. If Par.
is set to COMM.CW, this bit also activates the Run
Enable signal.)
0
Inhibit operation. Enter
OPERATION INHIBITED.
4
RAMP_OUT_
ZERO
1
Normal operation.
Enter
RAMP FUNCTION GENERATOR: OUTPUT ENABLED.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits in force).
5
RAMP_HOLD
1
Enable ramp function.
Enter
RAMP FUNCTION GENERATOR: ACCELERATOR ENABLED.
0
Halt ramping (Ramp Function Generator output held).
6
RAMP_IN_
ZERO
1
Normal operation. Enter
OPERATING.
0
Force Ramp Function Generator input to zero.
7
RESET
0
⇒
1 Fault reset if an active fault exists. Enter
SWITCH-ON INHIBITED.
0
Continue normal operation.
8
INCHING_1
1
Not in use.
1
⇒
0 Not in use.
9
INCHING_2
1
Not in use.
1
⇒
0 Not in use.
10
REMOTE_CMD
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control enabled.
Reference and deceleration/acceleration ramp are locked.
11
EXT CTRL LOC
1
Select External Control Location EXT2. Effective if Par.
is set to COMM.CW.
0
Select External Control Location EXT1. Effective if Par.
is set to COMM.CW.
12
USER MACRO
CHANGE
0
⇒
1 User Macro 2 loaded. Effective if Par.
is set to COMM.CW.
1
⇒
0 User Macro 1 loaded. Effective if Par.
is set to COMM.CW.
12 …
15
Reserved
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...